STAFF REPORT
TO: THE HONORABLE MAYOR AND BOARD OF COMMISSIONERS
FROM: D.W. FLIPPEN, BUILDING AND ZONING OFFICIAL <3 •9
DATE: JANUARY 24, 2000
SUBJECT: ADOPTION OF NEW ELECTRICAL STANDARDS
ISSUE
Should the Honorable Mayor and Board of City Commissioners approve an ordinance that would
adopt the most recent issue of the National Electrical Code and Notice "M" of the Florida
Electrical Code?
BACKGROUND/DISCUSSION
The Florida Department of Community Affairs has adopted the 1999 National Electrical Code as
the State Minimum Electrical Code. The City of Ocoee is required to adopt the 1999 National
Electrical Code or continue enforcing our currently adopted 1996 National Electrical Code.
The 1999 National Electrical Code has been reviewed by our staff members and found to be a
stronger, safer code. Notice "M" of the Florida Electrical Code should be adopted as a
companion code to the 1999 National Electrical Code.
RECOMMENDATION
Staff respectfully recommends the adoption of an ordinance that would adopt the 1999 National
Electrical Code and Notice "M" of the Florida Electrical Code.
2,4,
PoWI
Protect Ocoee's Water Resources
ORDINANCE NO. 00- 03
AN ORDINANCE OF THE CITY OF OCOEE, FLORIDA
AMENDING SECTION 69-10 OF THE OCOEE CITY CODE
RELATING TO STANDARDS FOR THE CONTROL AND
REGULATION OF ELECTRICAL CONTRACTORS AND
ELECTRICAL CONSTRUCTION; PROVIDING FOR
SEVERABILITY; PROVIDING FOR CODIFICATION;
PROVIDING AN EFFECTIVE DATE.
BE IT ENACTED BY THE CITY COMMISSION OF THE CITY OF OCOEE,
FLORIDA, AS FOLLOWS:
SECTION 1. The City Commission of Ocoee has the authority to adopt this Ordinance
pursuant to Article VIII of the Constitution of the State of Florida and Chapter 166, Florida
Statutes.
SECTION 2. Section 69-10 of Chapter 69 of the Code of Ordinances of the City of
Ocoee, Florida, is hereby amended to read as follows:
§ 69-10. Adoption of standards.
To the extent not more permissive than this chapter, there is
hereby adopted by the city for the purpose of establishing and
prescribing rules and regulations for electrical construction,
maintenance and repair within the city, those certain standards
known as:
A. National Electrical Code, 1999 Edition, NFPA No. 70
4-996 NFPA No. 70 1999.
B. Notice "L" (1996 NEC) Notice "M" (1999 NEC) to the
Florida Electrical Code, as adopted by the Central Florida
Advisory Code Committee.
SECTION 3. Severability. If any section, subsection, sentence, clause, phrase or
portion of this Ordinance is for any reason held invalid or unconstitutional by any court of
competent jurisdiction, such portion shall be deemed a separate, distinct and independent
provision and such holding shall not affect the validity of the remaining portion hereto.
006.158863.3
SECTION 4. Codification. It is the intention of the City Commission of the City that
the provisions of this Ordinance shall become and be made a part of the Code of Ordinances of
the City; and that sections of this Ordinance may be renumbered or relettered and the word
"ordinance" may be changed to "chapter," "section," "article," or such other appropriate
word or phrase in order to accomplish such intentions; and regardless of whether such
inclusion in the Code is accomplished, sections of this Ordinance may be renumbered or
relettered and the correction of typographical errors which do not affect the intent may be
authorized by the City Manager, without need of public hearing, by filing a corrected or
recodified copy of same with the City Clerk.
SECTION 5. Effective Date. This Ordinance shall become effective immediately upon
passage and adoption.
PASSED AND ADOPTED this day of , 2000.
ATTEST: APPROVED:
CITY OF OCOEE, FLORIDA
Jean Grafton, City Clerk
(SEAL) S. Scott Vandergrift,Mayor
FOR USE AND RELIANCE ONLY BY
THE CITY OF OCOEE, FLORIDA; ADVERTISED ,2000
APPROVED AS TO FORM AND READ FIRST TIME ,2000
LEGALITY this day of , 2000. READ SECOND TIME AND ADOPTED
,2000
FOLEY & LARDNER UNDER AGENDA ITEM NO.
By:
City Attorney
-2-006.158863.3
STATE OF FLORIDA
DEPARTMENT OF COMMUNITY AFFAIRS
"Helping Floridians create safe, vibrant, sustainable communities"
1E11 BUSH
Governor STEVEN M.SEIBERT
Secretary
September 14, 1999
Dear Building Officials:
This is to inform you that the Florida Department of Community Affairs/ the Florida
Building Commission has adopted the 1999 National Electric Code (NEC) effective September
20, 1999. Based on this rule, as of September 20, 1999, the 1999 NEC is the state minimum
electrical code which you are advised to adopt and enforce as soon as possible.
Enclosed for your information are a copy of Rule 9B-3049 which adopts the 1999 NEC
and a letter concerning Fair Housing Act accessibility standards.
Thank you for your cooperation and should you need more information regarding this
rule, please feel free to contact the Building Codes and Standards Office at 850-487-1824.
Sincerely,
/!70
Mo Madani
Planning Manager
MM/bjs
Enclosures
2555 SHUMARD OAK BOULEVARD • TALLAHASSEE, FLORIDA 32399-2100
Phone: (850) 488-8466/Suncom 278-8466 FAX: (850) 921-0781/Suncom 291-0781
Internet address: http://www.state.fl.us/comaff/
FLORIDA KEYS
Area of Critical State Concern Field Office GREEN SWAMP
2796 Overseas Highway,Suite 212 ---Area of Critical Stale Concern Field Office
Marathon,Florida 33050-2227 205 East Main Street,Suite 104
Bartow,Florida 336304M41
Printed and Distributed by the Florida Association of Electrical Contractors Central Florida Chapter
FLORIDA ELECTRICAL CODE case of emergencies,there shall be a shunt trip switch installed on the
Central Florida Advisory Code Committee exterior of the building or structure. The shunt trip switch,when
Notice"M"(1999 NEC) installed,must meet all the installation requirements of the outside main
disconnecting means. A sign constructed of permanent materials with no
The iollowing interpretive additions to the National Electric Code 1999 less than 1—1 high letters designating"Shunt Trip—Main Disconnect"
and the interim amendments thereto(latest edition of NFPA)have been shall be located on the exterior of the building or structure,and approxi-
approved by the Central Florida Advisory Code Committee. mately one foot(1') radius of the shunt trip.
The chapter and paragraph numbers arc referenced to the 1999 NEC 250-66: Table 250-66, A grounding electrode conductor shall be a
(NFPA 70-1999) minimum of#4 bare solid copper. Also,a listed,identified ground rod
at the meter location shall he used as per 250-50.
The following is a list of participating authorities:
Town of Monteverde City of Casselberry 250-118: An equipment grounding conductor shall be provided in all
City of Ocoee City of Sanford electrical raceway systems to insure electrical continuity and shall have
City of Winter Park City of Oviedo the capacity to conduct safely any fault current likely to be imposed.
City of Lake Mary City of Titusville
Lake County Orange County 280: Surge Arrestors shall be listed and labeled,by a nationally
City of Longwood City of Maitland recognized testing lab,and installed on all permanent services.
City of Orlando City of Winter Springs
City of Winter Garden Seminole County 300-1(a):Approved raceways or AC&MC shall be required for all
City of Umatilla City of Apopka wiring used to conduct current for light,heat and power in churches,
Mount Dora City of Altamonte Springs schools,theaters,public buildings,manufacturing facilities,transient
City of Winter Haven type occupancies,commercial establishments of all kinds,apartment
building over three(3)floors,recreation rooms,laundry rooms,and
110-14:Inhibitor(or suitable approved reduction agent)shall be applied similar buildings, and underground wiring in connection with all
to aluminum connections#8 wire size and larger. apartments,condominiums and other above listed premises. Article 318
and 328 would be an acceptable exception to use when installed as the
210-50:There shall be a minimum of two(2)duplex receptacles in each code requires.
office,and classroom. They shall not be located on the same wall and
shall be separated by a reasonable distance to provide access from 333&334:Armored cable and metal clad cable are approved for use
different areas of the room. when an equipment grounding conductor sized by table 250-122 is
included with the cable assemble.
220-16(a):There shall be a maximum or two duplex receptacle outlets
installed on each of the two required small appliance receptacle branch 336-6(d):Non-Metallic sheathed cable(romex)shall not be run on top of
circuits in the kitchen. ceiling joists or truss bottom cords where the vertical clear space is over
42"(forty-two inches)unless protected from physical damage.
220-3(b)(9):The maximum number of outlets per 15 and 20 ampere
circuit on residential buildings shall be ten light outlets or six duplex 430-101(b):Ungrounded leads:A disconnecting means shall be installed
receptacle outlets or a combination of not more than five receptacle within sight and easy reach of electrically operated mechanical compo-
outlets and three light outlets The minimum size branch circuit for nents. The disconnecting means shall in no case be installed farther than
convenience receptacle outlets and general lighting on commercial 6 feet from the service side of the equipment. Mechanical equipment
classified work shall be 20 amp. shall include but not be limited to,electric furnaces,duct heaters,
The maximum number of outlets per 20 ampere circuit on commercial compressors,condensing units and air handling units.
classified work shall be six receptacle outlets. A 120 volt receptacle,a switched lighting outlet with lamp shall be
installed within three(3)feet of the servicing side of the heating and air
230-28: Masts for supporting service drops and service entrance conditioning equipment in attics,crawl spaces and isolated equipment
conductors shall be a minimum of two-inch rigid steel conduit or IMC. rooms,where mechanical equipment ma need servicing.
Masts exceeding three(3)feet above the roof may require guying. There
shall be no couplings in any free air portion of the mast above the roof 600-6:Disconnect required at the sign location and within sight.
line. **EXCEPTIONS:Orange County,Longwood and Seminole County;
NEC requirments as stated.
230-70(a):The service disconnecting means for residential services shall
be installed on the outside of the building. 680-8:Overhead conductor clearances,delete exceptions for clearances in
table 680-8.
230-71(a): No building shall have more than one(1)main service
disconnecting means. Six(6)motions of the hand arc acceptable instead 7(X)-I:In other than one and two family dwellings,emergency lighting
of one(I)main service disconnect provided they arc grouped together or shall be required to illuminate the area of electrical main distribution
in the same enclosure and not in violation of article 384-16. equipment when installed indoors.
For commercial buildings,the 100 amp or over service disconnecting
means shall be installed on the exterior of the building,or structure,and 725-15:All bell ringing transformers shall be located at the load center or
as near as the point of entrance of service conductors as possible. Upon an accessible place and the secondary wiring shall not enter the same box
special application to the inspecting authority,before any work is with the primary wiring. The bell or chime transformer may be placed in
started,approval may be granted for the meter and/or service disconnect- an approved manner on the ceiling or over the door of a closet and shall
ing means to be installed inside the building or structure,and be available be accessible. It shall not be installed in the attic,and it shall no be
for meter reading,servicing,and disconnecting in case of emergencies. installed less than six(6)feet above finish floor.
When the service disconnecting means is located at a point that is not
accessible and available for meter reading,servicing,and disconnecting in
EXCEPTIONS: City of Titusville-Recognizes Exceptions#1 and#2 to#680-8.
Seminole County,Longwood, Winter Springs,Winter Garden, Lake County-With the exception of conductors for residential and
Lake Mary,Casselberry,City of Oviedo,City of Apopka,City of commercial services and panel feeders,aluminum wire conductor shall
Winks Park,City of Altamonte Springs,Winter Haven-Prohibits not be installed and used in any residential,commercial or other structure
the use of aluminum wiring with the exception of No.I A.W.G.and larger with the exception of No.6 A.W.G and larger conductors for circuits
conductors for residential and commercial services and panel feeders. which originate from a panel and terminate at a single device:
and all electrical wiring in commercial or industrial buidlings shall be in
City of Maitland-The use of copper wiring and copper appurtenances conduit or raceways.220-3-B(9)of this notice applies or NEC
thereto is mandatory within the City of Maitland,to specifically exclude requirements.
any use of aluminum wiring and aluminum appurtenances thereto;such
regulations to apply to any existing buildings wherein electrical work is 336-6(D)Non-Metallic sheathed cable(romex)may be run on top of
replaced,repaired or added to,as well as new installations.This ceiling joists or truss bottom chords where the verticle clear space is 42"
provision applies throughout the code. (forty-two inches)or less measured from the bottom of the top chord to
the top of the bottom chord. Romex does not need to be fastened within
City of Ocoee-Copper wiring and copper appurtenances thereto are the 42"clear space.Where the vertical clear space is over 42"NEC
hereby made mandatory in or attached to any residential,commercial or conditions apply. See 333-12.
other building hereafter altered,build,constructed,erected,repaired,
replaced or moved into the City.The use and/or installation of aluminum
wiring and aluminum appurtenances thereto is specifically prohibited in City of Umatilla-National Electrical Code, 1990 edition or subsequent
or attached to any residential,commercial or other building hereafter editions,published by the National Fire Protection Association,Quincy,
altered,built,constructed,erected,repaired,replaced or moved into the Massachusetts,effective November I, 1990,with one amendment(A)
City. and two exceptions(B)and(C)as follows:
City of Sanford-Aluminum conductors shall not be installed and used A)Conductor Protection;Receways.All buildings,additions,and other
in any residential,commercial or other structures hereafter altered,built, structures shall have all electrical conductors used for the purpose of
constructed,erected,repaired or moved into the City of Sanford,Florida, carrying lighting or power current over fifty(50)volts AC installed in a
with the exception of No.6 A.W.G.and larger conductors for circuit listed and approved raceway.This requirement shall not apply to single
which originate from a panel and terminate at a single device. and two-family dwellings or their accessory structures.
City of Winter Park- I)210-52(d)-Outdoor Outlets-at least two(2) B)Aluminum Wiring.The use of aluminum wiring in construction in the
outside receptacle outlets accessible at grade level,(one in front and one City of Umatilla shall be prohibited.
in the rear).
C)Wiring.Any wire smaller than number twelve(12)is prohibited for
City of Winter Park and Winter Garden-2)210-52(g)-For a one use in construction in this City.
family dwelling we will require at least two(2)receptacle outlets in a
two-car garage or larger at a minimum of sixteen feet (16')apart in D)Electrical disconnects.
addition to any provided for laundry equipment. (1)All structures constructed after the date of adoption of this
section shall be required to have an electrical disconnect located outside
Winter Garden-422-18(c)A ceiling box in a bedroom is required to be of the structure and easily accessible by the City Utilities Department
installed for ceiling fan use to be supported in accordance,with the box and/or fire department.The electrical disconnect may be locked with a
marked as such for inspection. lock approved by the Fire Chief or his appointed representative.
(2)If the electrical meter is replaced,repaired or modified or if
Mount Dora-National Electrical Code.Whereas,the National Electrical an electrical permit is obtained on an existing structure it shall be required
Code, 1996 edition,allows the use of#14 gauge wire,fifteen-amp circuit to have installed an electrical disconnect located outside of the structure
breakers,and sixty-amp service,these practices shall be prohibited and easily accessible by the Utilities Department and/or fire department.
within the city and the following uses shall be adopted: (3)A structure is defined for the purpose of this Chapter of
the Code as any building that has electrical service.Electrical disconnect
I.All structures must be wired in a minimum of#12 gauge wire. is a fused electrical disconnection or circuit breaker that will terminate the
2.No structure shall use any circuit breakers more than twenty(20) electrical current flow to the structure either from an overload situation
amps on#12 gauge wire. or from being manually disengaged.The disconnect shall be a minimum of
3.No structures shall have a service less than one hundred(100)amps one hundred(100)amp capacity and shall be installed on the outside of
and shall have an outside disconnect. the building not more than seven(7)feet of the meter.
4.No aluminum conductor shall be installed and used in any residential,
commercial or other structures build,constructed,erected,substantially City of Altamonte Springs-
altered or moved within the city. I)Verify N.E.C.Edition adopted locally and Code Notice.
5.All electric motors five(5)horsepower or more shall be three-phase
where three-phase service is deemed necessary or reasonably available by ***The following municipalities require all new electrical services to be
the city. underground by City Ordinance: City of Altamonte Springs,City of
6.Two(2)ground rods,6'or more apart and continuous looped. Maitland,City of Winter Park,City of Ocoee,City of Winter
Garden and City of Apopka.
City of Oviedo,Seminole County,Winter Haven- Fixtures on
ceilings of 7'-0"clear height may extend below the ceiling provided a
clearance of not less than 6'-8"is maintained.Keyless and other bare bulb
type fixtures shall not be allowed below 6'8".
The Orlando Sentinel,Thursday,February 3.2000 K-3
NOTICE CIOF TY PUBUC
UC HEARING - -
OFE
is hereby given pursuant to Arti-
jll of the Constitution of the State
of Florida and Section 166.041,Florida
Statutes,that the Ocoee City Commis-
sion will hold a public hearing inte
Commission Chambers,City
locat-
ed at 150 N.Lakeshore Drive,Ocoee,
Florida during a reegular session to be
pm,or as soon thereafter asp possible,
I in order to consider the adoption of the
following ordinance:
ORDINANCE NO.00-03
AN ORDINANCE OF THE CITY OF I
• OCOEE,FLORIDA,AMENDING SEC-
TION 69-10 OF THE OCOEE CITY
. CODE ING TO STANDARDS
FOR THE COTNTRO AND REGULA-
TION OF ELECTRICAL CONTRAC-
STRUCTION; LECT
TORS ANDEPROVIDING ICAL CON-
STRUCTION;
SEVERABILITY; PROVIDING FOR
CODIFICATION;PROVIDING AN EF-
FECTIVE DATE.
Interested parties may appear at the
meeting and be heard with respect to
the proposed action.A copy of the pro-
posed ordinance may be examined in
the office of the City Clerk at City Hall,
150 N.Lakeshore Drive,Ocoee,Florida,
between the hours of 8:00 a.m. and
5:00 p.m.,Monday through Friday,ex-
cept legal holidays.
NOTICE: Any person who desires to
appeal any decision made by Commis-
sion with respect to any matter consid-
ered at such meeting will need a record
of the proceedings and for such pur-
pose may need to ensure that a verba-
tim record of the proceeding is made,
which record includes the testimony ,,
and evidence upon which the appeal
based.Persons with disabilities need-
ing assistance to participate in any of
these proceedings should contact the
Lake-
shoreOffice of th Drive,Ocoee, FL 34761, (407)
656-2322 Ext. 1023, 48 hours in ad-
vance of the meeting.
Jean Grafton,City Clerk
February 3,20002000
OLS3123043