HomeMy WebLinkAboutItem #07 Approval to Reallocate Existing Capital Budet Funds of $15,000 to Purchase Power and AC Backup UnitsD 0 C 0 (>- (? florlda AGENDA ITEM COVER SHEET Meeting Date: August 4, 2015 Item # ­7 Reviewed By Contact Name: Al Butler, Support Services Department Director: Contact Number: 407 - 554 -7063 City Manager: Subject: Authorization to reallocate existing capital budget funds of $15,000 backup units for the City Hall Server Room at a total cost of $11,791.80 modifications to install and use these units. and to make internal Background Summary: The FY 2015 Budget established a capital construction project to install a fire suppression system in the City Hall Server Room at a cost of $15,000. This budget level was based on a price quote secured by staff at the time the budget item was proposed. When this project was actually put out for bids, the only offer was at a cost of $32,000 —an amount that cannot be justified given the construction of a backup data center at Police Headquarters that would allow us to recover critical operations and data in case of a fire at City Hall. With the original intent not being feasible, staff seeks to address the next critical need for the City Hall Server Room, which is to provide power backup and a standby air conditioning unit. During the past year, both power interruptions and one air conditioner unit failure have occurred, with the result that critical servers lost power or overheated and shut themselves off. The power issue is caused by the Server Room not being completely on generator backup circuits. The existing group of small battery backups (aka, uninterruptible power supply or UPS) is capable of extending operations for only about 30 minutes and not all systems can be accommodated. The power capacity of existing generator- supported circuits is not adequate to support the total power demand, which will only increase as additional storage units are put into operation. The air conditioning unit in the room is barely adequate to meet existing needs and the room heats up quickly when the AC unit stops running. Staff investigated the marketplace for both large- capacity UPS products and portable cooling units. Of the many options available, three UPS units and two AC units were selected for additional analysis. Based on performance and pricing, staff selected the TX90 10 kVA UPS and CoolCube 12 cooling unit, both from Xtreme Power Conversion. In addition to providing the best performance, these were also the lowest cost products in each category. Other products considered were the Liebert APS 10 kVA UPS from Presidio, the CyberPower Smart App Online OL10000RT3UTF from Moon Tech (via Amazon), and the Liebert PFH037A -PL7 outdoor condensing unit paired with the DataMate DME037E -PH7 from Innovative Support Systems, Inc. Staff also considered installing a 3 -ton Panasonic wall- mounted unit at a cost of about $7,000. Along with the UPS, staff recommends that a four - module UPS parallel bypass switch be used to allow future expansion of the installation as power needs grow. Both the UPS and the AC unit can be readily moved to another location. Some re- wiring will be required to integrate the UPS into the building's power system. Working with the city's Public Works Department, circuits connected to the existing backup generator will be extended to the Server Room and connected to the input ports on the UPS. A secondary panel will be used in the room to provide UPS - filtered power to all outlets and to the backup AC unit. (The existing AC unit is already on a generator circuit.) The standby cooling unit includes accessories to allow automatic start-up and to exhaust hot air into the plenum space above the suspended ceiling. The UPS will bridge the time period for generator start-up during power failures. Issue: The city needs to acquire a UPS capable of providing backup power and a standby /supplemental cooling unit for the entire City Hall Server Room. Recommendations Staff recommends that the City Commission authorize the purchase of an Xtreme Power Conversion TX90 10 kVA/9 kW scalable online isolated UPS with four -unit parallel tie panel at a cost of $6,946.80 and an Xtreme Power Conversion CoolCube 12 cooling unit with accessories at a cost of $4,845.00, both from Creative Power Solutions. The portability of the CoolCube 12 unit adds to its value, as it can be used in multiple locations. The balance of the original project budget of $15,000 would be used to pay the costs of making changes to the City Hall power system to make the greatest possible use of the UPS and to supply conditioned backup power to all outlets in the Server Room. Attachments: Price quotes from Creative Power Solutions, Presidio, Moon Tech (via Amazon), and Innovative Support Systems, Inc., along with descriptive materials on each unit examined by staff. Financial Impact: This procurement has no impact on the adopted budget except to change the purpose for which the funds are to be expended. The cost will be covered by the existing Support Services Capital Improvements budget line item (Account No. 001 - 518 -00- 6302), which may need to be allocated to various accounts depending on the specific goods and services to be acquired. Any additional funds needed to complete the project will come from existing budget sources in Cost Centers 516 and /or 518. Type of Item: (please mark with an 'Y) Public Hearing For Clerk's Dent Use: Ordinance First Reading Consent Agenda Ordinance Second Reading Public Hearing Resolution Regular Agenda X Commission Approval Discussion & Direction Original Document/Contract Attached for Execution by City Clerk Reviewed by N/A Reviewed by City Attorney N/A Reviewed by Finance Dept.) N/A 2 CREATIVE POWER 'MBSOLUTIONS Name /Address PO Box 1015 Groveland, FL 34736 352 - 429 -5086 352 - 255 -1496 City of Ocoee Attention: Jack Butler 150 N Lakeshore Dr Ocoee, FL 34761 Date Estimate No. Project 07/23/15 6501 �uote TX90 an... Item Description UPS Xtreme Power TX90 Series 10kVA/9kW Scalable Isolated Online UPS. System includes (1) TX90 -10k UPS module and Four Module Parallel Tie Panel. System is Scalable to 30kVA/27kW N +1 or 40kVA/36kW Capacity. Parallel Tie panel includes (4) 60A UPS Module Output Breakers and 200A System Maintenance Bypass Switch (Break Before Make). TX90 UPS Modules each include Internal 4 minutes Battery, Output Isolation Transformer, Internal Maintenance Bypass Switch (Make Before Break), Parallel Cable, two Communication Slots, Shutdown Software, Communication Cables, Emergency Power Off (EPO) and Casters. Voltage shall be 20OV -240V nominal input and 240/120V Split Phase (3 -wire plus ground) output. Selectable output voltages are 100V, 110V, 115V, 120V, 200V, 208V, 220V, 230V, 240V. 208/120V is available with 120V and 88V legs. Optional Load Breakers are available. TX90 Series be programmed as 50 -60HZ or 60 -50Hz Frequency Converter. Factory Trained onsite 5x8 Start -up is included (most USA locations). UL/FCC Approved; 3 -Year Full Warranty; UPS Module Dimensions: (1) 11.4 "W x 25.4 "D x 29.5 "H, (1) 340 lbs. Wall mount Parallel Tie Panel: 15.5 "W x 4.5 "D x 40.5 "H, 50 Ibs Quote valid fo 30 days. Page 1 Estimate Quantity Cost I Total 1 1 1 6,946.80 6,946.80 Total Estimate CREATIVE PO Box 1015 POWER Groveland, FL 34736 352 - 429 -5086 SOLUTIONS04C" 352- 255 -1496 Name /Address City of Ocoee Attention: Jack Butler 150 N Lakeshore Dr Ocoee, FL 34761 Date Estimate No. Project 07/23/15 6501 Quote TX90 an... l Item Description Quantity Cost Total Part Internal SNMP/WEB Card for use with T90 and TX90 1 177.00 177.00 Series UPS; Allows for monitoring and management of UPS through a web browser or SNMP platform: Provides shutdown of remote clients via LAN, and Email Notification of UPS status and events. packaging = 5.7 "W x 5.2 "D x 1.7 "H, 0.3lbs air conditioning With a revolutionary modular design that easily 1 3,000.00 3,000.00 unit adapts to virtually any application, MaxPower's CoolCube 12 is the only air conditioning solution in the industry that changes to fit your individual needs. The compact, 12,000 Btu /h module can be rack - mounted, hung from the ceiling, stacked for capacity or redundancy, or used as a stand -alone portable unit - simply by adding the respective accessory Contents: (1) CoolCube 12 Module, (1) Remote Control, (1) Unpacking Instructions Sheet, (1) Warranty Registration Card, (1) Operation Manual Part The CVK -8 is the field installed ceiling panel 1 180.00 180.00 conversion kit that converts the CK -8 into a two -duct ceiling panel, for both discharge and intake of condenser air above a drop ceiling. The kit is to be used in conjunction with the CCP -8 Quote valid fo 30 days. Total rl„nto lin ;A f— Qn .4­- Page 2 Estimate CREATIVE PO Box 1015 POWER Groveland, FL 34736 352 - 429 -5086 SOLUTIONSO(" 352- 255 -1496 Name /Address City of Ocoee Attention: Jack Butler 150 N Lakeshore Dr Ocoee, FL 34761 Date Estimate No. Project 07/23/15 6501 Quote TX90 an... Item Description Quantity Cost Total Condenser Return Air Plenum. Contents: (1) Discharge Baffle (1) 8 -inch Diameter Flex Duct, 120" Length (1) 8 inch Duct Flange (1) Duct Strap, 48" (4) #8 Thread Forming Screws * Duct flange comes pre - installed onto duct flange. Part The CCP -8 is the field installed condenser plenum 1 192.00 192.00 kit that allows for the ducted return of air to the condenser. The plenum has a filter rail, and is equipped with an 8 -inch duct round flange. Contents: (1) Condenser Plenum (1) 12/20 filter Part The CPC -1 is the field installed condensate pump 1 156.00 156.00 kit that allows for the collection and pumping of condensate from the CAC1211. The pump is capable of a 20 foot lift, and installs in the unit, in place of the condensate bucket. Contents: (1) 120V condensate Pump (with mounting bracket attached) (1) 5/8 -inch Corrugated Drain Hose Quote valid fo 30 days. Total (l inic v�lirl fnr Q(1 rlovc Page 3 Date Estimate No. Project 07/23/15 6501 �uote TX90 an... Item Part Part Start Up Description (1) 3/8 -inch x 25 ft condensate line (2) Hose clamps (1) 1 -1/8 -inch Spider bushing (1) 3/4-inch bushing (2) Sheet Metal Screws Remote Thermostat Kit 'Display Cable Sold Separately. Remote Display Cable 25ft for Cool Cube 12 UPS Start-up Normal Business Hours: 8:00am- 5:00pm Exempt Quote valid fo 30 days. ('li infc inaHrl fnr 4(1 r — Page 4 Quantity Estimate Cost 1 150.00 1 30.00 960.00 0.00% Total Total 150.00 30.00 960.00 0.00 $11,791.80 PO Box 1015 CREATIVE Groveland, FL 34736 CPOWER 352 - 429 -5086 S OLUTIONSOOI " 352- 255 -1496 Name /Address City of Ocoee Attention: Jack Butler 150 N Lakeshore Dr Ocoee, FL 34761 Date Estimate No. Project 07/23/15 6501 �uote TX90 an... Item Part Part Start Up Description (1) 3/8 -inch x 25 ft condensate line (2) Hose clamps (1) 1 -1/8 -inch Spider bushing (1) 3/4-inch bushing (2) Sheet Metal Screws Remote Thermostat Kit 'Display Cable Sold Separately. Remote Display Cable 25ft for Cool Cube 12 UPS Start-up Normal Business Hours: 8:00am- 5:00pm Exempt Quote valid fo 30 days. ('li infc inaHrl fnr 4(1 r — Page 4 Quantity Estimate Cost 1 150.00 1 30.00 960.00 0.00% Total Total 150.00 30.00 960.00 0.00 $11,791.80 XTREME POWER CONVERSION TX90 /T90 6kVA to 40kVA Parallel Scalable System Online scalable UPS for high power and critical N +1 redundant applications Xtreme TX90 and T90 parallel N +1 redundant online Uninterruptible Power Supply (UPS) provides the ideal solution for the most demanding critical power re- quirements. Configurations up to 40kVA can easily be configured using individual RVA or 10kVA modules. Xtreme N +1 configurations allow complete serviceabil- ity and redundancy. Should an individual UPS require maintenance, the UPS is automatically taken offline. A notification is provided to the user from the LCD display and an audible alarm. The failed UPS module may be serviced or replaced without the remaining UPS modules or connected load having to be powered down. For single module RVA & 10kVA systems, reference the TX90 /T90 at: www.xpcc.com /t6 -10 PRODUCT SNAPSHOT > Redundant and scalable UPS with an output up to 40kVA > Galvanic isolated systems (TX90) provide full electrical noise isolation and 120/240V split -phase output > Transformerless systems (T90) provide the most economical solution for 200V, 208V, 220V, 230V, and 240V applications > Optional extended battery banks & chargers FEATURES 0.9 output power factor — more wattage for high density loads Galvanic isolation transformer (TX90)— eliminates common mode noise and provides power conditioning during nor- mal and bypass operation 200 amp parallel tie panel — provides parallel tie and system maintenance bypass for up to four T90/TX90 power modules. Lockable casters— simplify installation and maintenance Hot swappable internal battery trays —UPS module batteries are easy to replace without interrupting the load UPS module bypass — allows individual module repair with internal mainte- nance bypass Extended battery runtimes — optional external battery cabinets and chargers can be added for extended runtime applications. MODEL SELECTION GUIDE OUTPUT Capacity Capacity (redundant) Voltage Scalable Voltage BATTERY Battery runtime (internal) PHYSICAL UPS dimensions (W x D x H) Number of UPS modules Optional external battery cabinets Tie panel dimensions (W x D x H) APPROVALS SYSTEM INCLUDES 6kVA (5.4kW) 12kVA (10.8kW) 18kVA (16.2kW) 24kVA (21.6kW) N/A 6kVA (5.4kW) N +1 12kVA (10.8kW) N +1 18kVA (16.2kW) N +1 208VAC or 240VAC All models are scalable to 24kVA or 18kVA N +1 TX90: 240/120VAC or 100, 110, 115, 120, 200, 208, 220, 230, 240VAC selectable* T90: 208VAC or 200, 220, 230, 240VAC selectable 6 minutes at 100% load / 17 minutes at 50% load 11.4 x 25.4 x 29.5 in 1 2 3 4 11.4 x 25.4 x 29.5 in (EBP960, EBP940, EBP920) 15.5x4.5x40.5in UL1778, cUL, CE, FCC A UPS modules with internal batteries, 200A parallel tie panel with 40A module output breakers, parallel communication cables. INPUT Capacity 10kVA (9kW) i 20kVA (18kW) 30kVA (27kW) 40kVA (36kW) ** UPS module Capacity (redundant) N/A 10kVA (9kW) N +1 20kVA (18kW) N +1 30kVA (27kW) N +1 Voltage 208VAC or 240VAC TX90 or T90 Scalable All models are scalable to 40kVA or 30kVA N +1 OUTPUT Voltage I TX90: 240/120VAC or 100, 110, 115, 120, 200, 208, 220, 230, 240VAC selectable* UPS module 90/T90 parallel sy: > -a_rn T90: 208VAC or 200, 220, 230, 240VAC selectable BATTERY Battery runtime (internal) 4 minutes at 100% load / 12 minutes at 50% load PHYSICAL UPS dimensions (W x D x H) 11.4 x 25.4 x 29.5 in (T90) 11.4 x 25.4 x 34.7 in (TX90) Number of UPS modules 1 2 3 4 Optional external battery cabinets 11.4 x 25.4 x 29.5 in (EBP960, EBP940, EBP920) _ Tie panel dimensions (W x D x H) 15.5 x 4.5 x 40.5 in APPROVALS UL1778, cUL, CE, FCC A SYSTEM INCLUDES I UPS modules with internal batteries, 200A parallel tie panel with 60A module output breakers, parallel communication cables. '2401120V Spht Phase (3 wire plus ground) a default output. Selectable voltages: 100V, 110V, 115V, 120V, 2001, 208V . 230V,, 240V. Two low voitoo ° »er tops moy be connected in parallel to provide a single full copocity 100V, 110V, 115V, 120V output. 208112OV is available with 88V leg. Please speolIy * *Xtreme parallel tie panel is limited to 160A. Utility input feed Utility Input Panel (provided by others) _.. TX90 or T90 UPS module _.. TX90 or T90 UPS module TX90 or T90 UPS module TX90 or T90 UPS module 90/T90 parallel sy: > -a_rn diagram Xtreme Power 200A Parallel Tie Panel Module output breakers 10kVA:60A 6kVA: 40A Maintenance bypass breaker 200A TX90: break - before -make T90: make - before -break Output to critical loads Load breakers are optional TX90: 240/120V* (L.i, Lz, N, G) T90: 208 or 240V (Li, Lz, G) XTREME POWER CONVERSION COOLCUBE 12 For more information, visit www.xpcc.com /ccl2 Cooling for Critical Electronics Modular air conditioning for critical electronics The CoolCube 12 is the only air conditioning solution in the industry that changes to fit your individual needs. With it's revolutionary modular design the CoolCube 12 easily adapts to virtually any application. The CoolCube 12's modularity gives it the ability to efficiently cool hot spots at their source making it the number one choice for IT environments. Whether your telecommunications room is a converted coat closet or a mechanical room, the versatile Cool- Cube 12 is ideal for any location, easily fitting into the infrastructure of any building. The CoolCube 12 protects expensive IT investments from overheating. Studies have shown every 10°C rise in nominal temperatures results in a 50% reduction in the lifetime and long term reliability of IT hardware. The CoolCube 12 operates down to 65 °F, creating the perfect environment for your IT equipment. PRODUCT SNAPSHOT > Available model: 12,000 BTU /H > 5 year compressor warranty > Draws less than 10 amps in most applications > Provide cost effective, efficient, and mobile cooling > Standard with handle kit and casters > UL, cUL listed FEATURES Modularity — CoolCube 12 can be rack mounted, hung from the ceiling, stacked for capacity or redundancy, or stand -alone portable unit Compact 13U module —fits into an open 2 -post or 4 -post 19" rack, occupying just 13U of rack space Commercial grade —steel construction with heavy duty oversized casters Compact design — CoolCube 12 is 50% smaller than competitors Condensate pump — optional condensate pump kit installs in moments with quick plug connection Automatic restart —unit re- starts automatically when power is reapplied after an outage R410A refrigerant -earth friendly refrigerant does not deplete the Ozone like R22 MODEL SELECTION GUIDE COOLING Cooling capacity Air flow (high /low) evaporator Air flow condenser Refrigerant ELECTRICAL Power supply voltage Power supply frequency Current consumption Circuit breaker size Power consumption NEMA plug For more information, visit www.xpcc.com /cc12 12,000 BTU /H 400 /320 CFM 490 CFM R410A 115VAC 60Hz 12A 15A 1180W 5 -15P 10 ft Unit automatically restarts when power is reapplied after outage 17.3 x 24.0 x 20.0 in 133lbs 65- 105 °F 8 in 2 gal UL, cUL 1 year system (USA), 5 year compressor warranty Auto restart - CoolCube 12 will restart to the last set point automatically when power is reapplied after an outage Fan speed - In AUTO mode, the evaporator blower will adjust air flow automatically for added comfort and performance. In MANUAL mode and the evapo- rator blower will run continuously at one of six levels of fan speed. Moisture control - The system operates in the cool- ing mode to reduce humidity within the conditioned space. Power cord length Automatic restart PHYSICAL Dimensions (W x D x H) Weight Operating conditions Hot air duct diameter Condensate tank capacity APPROVALS WARRANTY COOLCUBE 12 ACCESSORIES Model Description CK -8 8 in ceiling discharge kit CVK -8 Ceiling panel conversion kit CPC -1 115V condensate pump kit CNK -1 2 in x4 in nozzle kit CDA-8 8 in discharge adapter CEP-6 2 in x 6 in evaporator return plenum CCP-8 8 in condensate return plenum CFK -1 Feet kit CRD -1 Rack diffuser SK -1 Stacking kit RCK-1 19 in rack installation kit RTK -1 Remote thermostat kit 012 -009 Remote display cable, 25 ft 012 -010 Remote display cable, 50 ft 012 -008 Remote display cable, 75 ft 012 -020 Remote temp sensor, 25 ft For more information, visit www.xpcc.com /cc12 12,000 BTU /H 400 /320 CFM 490 CFM R410A 115VAC 60Hz 12A 15A 1180W 5 -15P 10 ft Unit automatically restarts when power is reapplied after outage 17.3 x 24.0 x 20.0 in 133lbs 65- 105 °F 8 in 2 gal UL, cUL 1 year system (USA), 5 year compressor warranty Auto restart - CoolCube 12 will restart to the last set point automatically when power is reapplied after an outage Fan speed - In AUTO mode, the evaporator blower will adjust air flow automatically for added comfort and performance. In MANUAL mode and the evapo- rator blower will run continuously at one of six levels of fan speed. Moisture control - The system operates in the cool- ing mode to reduce humidity within the conditioned space. PRESID10 City of Ocoee FROM: Presidio Networked Solutions Accounts Payable QUOTE: 20015115003147 -01 150 N. Lakeshore Drive 5337 Millenia Lakes Blvd. Ocoee, FL 00000 Suite 300 DATE PAGE 07/20/201 1 of 2 TO: City of Ocoee FROM: Presidio Networked Solutions Accounts Payable Susan Bacci 150 N. Lakeshore Drive 5337 Millenia Lakes Blvd. Ocoee, FL 00000 Suite 300 Orlando, FL 32839 (p) (407) 905 -3100 Ext. 1523 sbacci @presidio.com (p) 407.641.0563 Customer#: CITY0262 Account Manager: Ross LoBrutto Inside Sales Rep: Susan Bacci Title: City of Ocoee - 101kVA Description Unit Price City Ext Price 1 10kVA APS Single Phase One (1) Liebert APS UPS System rated at 10 kVA/9.0 kW with 5 minutes backup time. $9,061.10 1 $9,061.10 UPS Model AS5BONCVGNNX887, single phase 120/208 input and output, with the following features: Comments: On -line double conversion design with a sine wave output N +x parallel redundancy to provide a fault tolerant network of power protection for continuous systems availability Quoted model is configured Non - redundant Input and output noise suppression Main input, output, and internal maintenance breaker Input power factor 0.99 6 hour battery recharge time to 90% capacity Fault tolerant microprocessor -based control and monitoring Low voltage distortion output inverter Flame- retardant, Sealed valve regulated batteries LCD display module with mimic diagram of power flow and provides digital metering, event logging, user customize -able set points (low battery alarm, battery test, auto - restart delay, display language) All modules are hot - swappable to provide maximum system flexibility and availability Casters and leveling feet WEEE, REACH, and RoHS (6 by 6) compliant Integral output distribution providing None outlets Integral output distribution providing None outlets * Units are capable of rack mounting with optional rack mounting kit * UPS frame is designed for maximum of 15 kVA, 208/12OV, 60 Hz, L- L -N -PE UL 1778 4th Edition, c -UL, Listed (1) IntelliSlot Velocity /Life.Net Card; P /N: IS- UNITY -DP; Offers a web interface to monitor and configure the Life.nel and Emerson Network Power proprietary protocols for use with the Emerson Life Station, Liebert Worm and Emerson Trellis. It allows you to select and configure two of the available third party protocols — SNMP, Modbus or BACnet for interfacing to Building Management Systems. UPS System Services Include: Start-up service includes one site trip by a Liebert Services customer engineer after the unit has been installed. The site trip includes the following services for each system: non - powered inspection, unit electrical and operational checkout, full parts and labor for any work required on the unit, and basic customer operation training. Start-up also provides the customer with a guaranteed 6 hour on -site response for emergency service and includes onsite labor, parts, and travel for the full two-year warranty period. Warranty Inspection Start-Up to be provided between the hours 0800 and 1700 Monday to Friday, business days Sub Total: $9,061.10 Grand Total: $9,061.10 QUOTE: 20015115003147 -01 PRESID10. PAGE: 2 of 2 Quote valid for 30 days from date shown above. Prices may NOT include all applicable taxes and shipping charges. All prices subject to change without notice. Supply subject to availability. This quotation subject to Presidio Standard Terms and Conditions as follows Credit: Net 30 Days (all credit terms subject to prior Presidio credit department approval) The price included herein reflects a 3% discount for payment by cash, check or wire transfer. This discount will not apply in the event that customer pays using a credit card or debit card. Delivery: FOB origin (FOB destination (CONUS) applicable to Federal Government Customers only) Orders shipped from a manufacturer to Presidio at customer request for warehousing, configuration, storage or otherwise, shall be deemed to have been shipped to customer FOB origin. Changes to the above Terms and Conditions must be accepted in writing by Presidio Networked Solutions Preprinted terms appearing on Customer Purchase Orders must be accepted in writing by Presidio Networked Solutions to be applicable. Size Business: Large, CAGE Code: 0K1)05; DUNS 15- 405 -0959, CEC: 15- 506005G; Tax ID# 58- 1667655 Product is warranted by the Manufacturer, not by Presidio Networked Solutions. Please consult Manufacturer for warranty terms. Opened product is non - returnable. Unopened equipment is non - returnable after 30 days from shipment date. Presidio reserves the right to deny RMA requests in the event the Manufacturer will not provide for an authorized return. If integration of product is performed at a Presidio facility, transfer of ownership occurs as of inception of integration regardless of shipment terms as manufacturers will not accept return of open product. Please inspect equipment thoroughly against packing list before opening. Pricing for Professional Services are best -effort estimates only. Actual pricing will be finalized as part of a mutually-agreeable Statement of Work. Import Clearance and Documentation - Customer shall be responsible for the Customs clearance process, where applicable, and for obtaining any and all required license and permits as well as satisfying any formalities required to import the Products into the Territory in accordance with all applicable laws and regulations, including but not limited to the payment of duties, taxes, surcharges, fees and any special assessments and take all other actions required in connection with the importation and Customs clearance of Products. Customer shall be responsible for ensuring documentation necessary for the import and Customs clearance process and recordkeeping meets all applicable laws and regulations. Export Controls - (i) Customer shall comply with all applicable Export Control Laws, including but not limited to the U.S. Department of Commerce's Export Administration Regulations, in the performance of this Agreement and in the import, export, re-export, shipment, transfer, use, operation, maintenance, repair or disposal of Products and any related parts, components, accessories, know -how or technology. 'Export Control Laws' means all export control, economic sanction and antiboycott laws and regulations of the United States and other jurisdictions, including but not limited to the U.S. Export Administration Regulations, the U.S. International Traffic in Arms Regulations and the U.S. Department of Treasury's economic sanctions regulations. (ii) Product and any related parts, components, accessories, know4ww and technology must not be re-exported or transferred to restricted persons and sanctioned countries designated by the U.S. Government, including Cuba, Iran, North Korea, Sudan and Syria, unless authorized in advance by the Company and the U.S. Government. (iii) Customer acknowledge that transfers of Product and any related parts, components, accessories, know -how and technology may be subject to the terms and conditions of an export license, license exception or other authorization pursuant to Export Control Laws. Customer agree to comply fully with the terms of any licenses, license exceptions or authorizations and to provide Presidio Networked Solutions access to records needed to confirm such compliance upon request. (iv) Customer further acknowledges that certain Products may contain encryption and may be restricted for export, re-export, shipment or transfer to government end users in certain countries. Customer hereby authorizes and agrees to make timely payment for products delivered and services rendered, including payments for partial shipments Customer Signature Date Liebert APS UPS Liebert EBC Liebert APS 16 Bay 14 Bay Single Phase UPS XFMR Free External Battery Cabinet 15kVA/13.5kW Liebert 28 minute Battery Run Time APS ® • 208/120 volt, 2 phase MBC • ••••• • 5kVA/4.5kW 5kVA/4.5kW Power Module Power Module Battery Module Battery Module #t #2 #1A #'IB Liebert 15kVA APS UPS: Dimensions: 17.3 "W x 33.5"D x 38.1 "H 5kVA/4.5kW Spare Slot for Weight: 740 Lbs. Power Module Power Module Battery Module Battery Module Service Clearance: 39" in Front, 12" in Rear #3 #4 #2A #26 Heat Output: 6,768 BTU /hr Battery Module Battery Module Battery Module Battery Module #1A #1B #3A #3B Liebert EBC (External Battery Cabinet): I Dimensions: 17.3 "W x 28 "D x 381 "H Battery Module Battery Module Battery Module Battery Module Weight: 735 Lbs. #2A #26 #4A #4g Liebert APS Maintenance Bvpass Cabinet: Battery Module Battery Module Battery Module Battery Module Dimensions: 9.5 "W x 26.5 "D x 30.5 "H Wei ht: 85 Lbs. #3A #3B #5A I #5B I g Battery Module Battery Module #9 11 #4B Battery Module Battery Module V I I #5B Battery Module Battery Module #6A I I #6B Battery Module Battery Module #7A I I #7B Battery I � Battery Bodule I 1 s slls 9.5" 17.3" �� sl 17.3 hLiebert 'Masan C Rk.f P.— 6 Cooling T- hnobgiss' Innovative Support Systems, Inc. Project: Liebert 15kVA APS Single Phase UPS System s EMERSON.. Title: Cabinet Data, APS 16 Bay TX -Less Cabinet, 15kVA/13.5kW NeUvork Povier Date: 06- 24/2014 1 By: Sean Devaney I Drg# - Ocoee - MANUAL BYPASS INPUT OUTPUT L —L —N —G L —L —N —G (50/60Hz) EMI POWER EMI OUTPUT AND (50 /6OHz) FILTER MODULE(s) FILTER BYPASS CONTACTOR BATTERY MODULE(s) DRAWN BY SHEET NO. K. STACY 1 OF 1 ONE -LINE DIAGRAM CHK BY ECN NO. LIEBERT APS J. FUCHIK 15 /20KVA, 10/16 BAY 200/100- 240/120 V EMERSON_ REF. DWG. ORDER NO. 50 /60HZ 2PH XFMR -FREE UPS DWG. NO. I DATE I REV. # 1 1050 DEARBORN DPo� APS2002 12/23/13 1 COWMBU& OHIO 43229 Netwror Pb -ILE NAME: r- 17.3" [440mm] 14 FRONT VIEW �1 22.9" [581 mm] Ea � I 9.6" 6.9" [243mm] REAR VIEW = 31.5" [799mm] RIGHT SIDE VIEW 24.7" [6927mm] 27.4" [695mm] 3.6" [92mm] -� 1.0" [24mm] 1 1 6.1,. [154mm] 2.9" [72mm] 4.6" 'Oily r O' [117mm] [36mm] BOTTOM VIEW DRAWN BY SHEET NO. K. STACY 1 OF 1 OUTLINE DRAWING CHK BY ECN NO. LIEBERT APS J. FUCHIK 15KVA, 10 BAY, 200/100- 240/120V EMERSON_ REF. DWG. ORDER NO. 50 /60HZ 2PH XFMR -FREE UPS DWG. NO. DATE REV. # 1050 DEARBORN DPo� APS1003 I 12/26113 I 1 I COWMMM 01410 4432" Netwnit Po1w ILE NAME: DRAWN BY K. STACY CHK BY G. FUNK REF. DWG. —ll� 17.3" [440mm] ti FRONT VIEW 28.0° [712mm] 38.1 " [968mm] TTI r RIGHT SIDE VIEW 3.6" [92mm] 1 r-71 0" [24mm] 1 2.9" [154mm] [72mm] � T � 4.6" [117mm] 1.4" I� [3smm] BOTTOM VIEW DWG. NO. DATE REV. # 1 1050 DEARBORN DRIVE EMERSON.. P.O. OX APS1007 8/20/13 0 COLUMBUS. OHIO183229 Network Power FILE NAME: 0 REAR VIEW SHEET NO. 1 OF 1 OUTLINE DRAWING ECN NO. HEBERT APS 14 BAY EBC ORDER NO. 28.0° [712mm] 38.1 " [968mm] TTI r RIGHT SIDE VIEW 3.6" [92mm] 1 r-71 0" [24mm] 1 2.9" [154mm] [72mm] � T � 4.6" [117mm] 1.4" I� [3smm] BOTTOM VIEW DWG. NO. DATE REV. # 1 1050 DEARBORN DRIVE EMERSON.. P.O. OX APS1007 8/20/13 0 COLUMBUS. OHIO183229 Network Power FILE NAME: 0 0 ® UPSSHOWN FOR REFERENCE ONLY L•ST•�� /��'— 'GL�3T 4 � C e e 30" (762) MAINTENANCE BYPASS CABINET MAY BE POSITIONED TO LEFT OR RIGHT OF UPS NOTES 1) INSTALL IN ACCORDANCE WITH NATIONAL AND LOCAL ELECTRIC CODES. 2) ALL DIMENSIONS ARE IN INCHES AND (mm) 3) UNIT WITH TRANSFORMER REQUIRES GEC CONNECTION REFER TO THE INSTALLATION AND USERS MANUAL, SL- 23960. 4) INPUT AND OUTPUT WIRES SHOULD BE RUN IN SEPARATE CONDUIT. 5) MINIMUM OPERATIONAL CLEARANCE REQUIRED: 12' (305) FRONT AND REAR FLEXIBLE CONDUIT RECOMMENDED FOR SERVICE ACCESS. 6) SHIPPING BRACKETS MAY BE USED TO SECURE UNIT TO FLOOR. 7) PALLET DIMENSIONS: 3TW x 42 5'D x 9 "H (914 x 1080 x 228) 8) MAX WEIGHTS - UNIT WITH ISO TRANSFORMER 275 LBS (125kg), SHIPPING WEIGHT 350 LBS (159kg) UNIT WITHOUT ISO TRANSFORMER: 85 LBS (39kg), SHIPPING WEIGHT 160 LBS (73kg) BYPASS SWITCH DOOR LATCH AND LOCKOUT PROVISIONS OUTPUT BREAKER S UPS OUTPUT INDICATOR � e BYPASS INDICATOR BYPASS SWITCH UPS INPUT INDICATOR 30.4 UPS INPUT BREAKER • • (7755) e tl CONFIGURABLE OUTPUT HARDWARE OUTPUT (STANDARD) e • INPUTS TO • UPS UTILITY INPUT OUTPUT FROM UPS m�T7 9.5" 26.5" (3) 1 -1/4" CONDUIT (241) ~ (700) -� FRONT SIDE DRAWN BY SHEET NO. R LYLES 1 QF 1 OUTLINE DRAWING CHK BY ECN NO. MAINTENANCE BYPASS CABINET (MBC) J GRFTZ CONDUIT CONNECTIONS NFINITY /UPSTATION GXT REAR REF. DWk, ORDER NO. e tl CONFIGURABLE OUTPUT HARDWARE OUTPUT (STANDARD) e • INPUTS TO UPS UTILITY INPUT OUTPUT FROM UPS (3) 1 -1/4" CONDUIT CONNECTIONS . 0 0% -� (2)1/2 "CONDUIT CONNECTIONS 4.8" MAIN INPUT, 1 -1/4" & 2" CONDUIT CONNECTIONS REAR DWG. NO. MNF000 -01 REV. NO. DATE N 1 7/14/04 FILE NAME MNFOOO-01 �i Liebert EMERSON. P.O. BOX 29188 COLUMBUS, OHIO 43229 NE&AD& ' >) 1 no] � (< K. STACY 1 OF 1 no� �< ECN NO. \� G. FUNK e 15KVA, 10 BAY, 200/100- 240/120V REF. DWG. ORDER NO. 50 /60HZ 2PH XFMR -FREE UPS - �) oil �( IuuJ ( o1: IooJ //, \C�) u, Ioo • 3 Il \ 1�) • �• e • }e �J BATTERY CABINET LIEBERT APS FRONT VIEW DRAWN BY SHEET NO. K. STACY 1 OF 1 LINE UP DETAIL CHK BY ECN NO. LIEBERT APS G. FUNK 15KVA, 10 BAY, 200/100- 240/120V REF. DWG. ORDER NO. 50 /60HZ 2PH XFMR -FREE UPS •t,A�J � �• v0000 oa___ __,__ - - - - -- • a :eeo 000mo - - - -- - - - -- - - - -osoo - I------------ - - - -- - - - - - - - - - - ----- --- - ------------ - - ----- ..... ----- ----- LIEBERT APS BATTERY CABINET REAR VIEW DWG. NO. DATE REV. # 1050 DEARBORN DRIVE EMERSON APS4003 8/21113 0 COLUMeus OHIO 43229 Network Power -ILE NAME: B 7 1 6 5 0 MAINTENANCE BYPASS ONm — _ _ _ THESE ( LINKS WITHOUT TRANSFORME 0 1R NOT REIEASED rz). t FORWAL NPUT FEE0 RELEAD IOR PROOUCTKNJ yty� 0.wEB6TER TB/ ADDED CHART C AND NOTE R OVER T J] 2 CBt FOR CONNEGTKIN LPs MOO 0. FEEDER � — — .� / � — , I CORRECTEOIPS UNT GE� p tsff OHeeTq �' — — — L1 IAYP] I IA8P1 —( M IGVEDTDT B]I CORRECTED NIBS UNIT GNDA, p SSE 1 ADDED CHITS DBE TOCLARIFY SWI Tall S OROIMD �0 SINGLE DUAL FEED I DUAL FEED CONFIG. 1 — — — — oEn I I I .wa Cal Z' I s OU UTILITY s- POSITION I OUTPU- (T.) I FIGURATIONS Ecry E1BB2s7 1 761 (UPS FEEDER 14 3C �pV IIJTIB7 BYPASS FEEDER ONYJ 1J7•J2,IR REMOVED I I I I _� 2�u 2W.2� N.GNC U� I 1a 208V 1 IJ] I 1 OUT 1J 1ADV' 1 A yJ TO LOAD I td,3 1NN I TB2 ISEECNrRTN BYPASS 1 24 208V 1 MAHWM I J I I I "' �e I ) '� J I 1. 208V• 1 MEDERO L1 L J _ - -L_ TOOPTIONONLYON UPS I 2a 208V• I AU X SWITCH TB8 MODELS NMBNMW 2tl, 2. +N. ONO I 1a 2M I CHART NRT 1 c — — J S AND NMSHlVN1 4.3 12V 1 — SINGLE FEED CONFN;. — uwP2 I NC I BYPASS I 2a 2MV• I I T81 1NOCONNECTION _ — _ Np I IN 1DOJ I 1782 UPS 6 BYPASS FEED I �] �nFRI THESE VOLTAGES CIUNGE BASED ON IJ1• J2, JUMPERS FACTORY TBA SW11N UPS DR BYPASS POSITKIN IJ3 (INSTALLED � J_ 1 TB] L1 2 2 _ ] CHART CHART C UT LYRCIATBREAKER M NFINTf Y UPS B INP ICSIJONLYNNSTALLEDIN 2dSp I 4.16KVA UPS UNITS 20KVA UPS UNffB a 1NLVA UPS UNITS. 1 N'BUT CIRCWTBREAKHI 1 NO, OF NO, OF NO* OF W. OF FOR "VA UPS UNITS IS FRAME BATTERY POWER FRAME BATTERY POWER CUSTOMER PRONGED S� MODULES MODULES 8� MODULES MODULES TBt UPSTREAM. PavER ­E INTELLIGENCE x� �T _ 18 BAY 7 MAX 8 MAX I 112 BAY 11 MAX S MAX 2 m Cal /� _ �pAIT 112 BAV 11 MAX 6 MAX 2 I 1 FILTER FIETTER r •� / £ I rl rL •� ,U n T ` ^2 e & c DOMTACT00. OND 3 �5 TOAPPROVED I DEC I SGECCONNECTK]N f COMMMON GROUND BATTERYM EINTERFACE rAFi l i CONTROL MDDJLE INTELLIGENCE Fj I — I -� OPipNAI SECOFDCONTROL NOIXILE F+ I — L 1 USER INTERFACE F� I I R41A "'"Y auw"'roHO I w.vcu,Ma wosm.nR� L _ coFNECTDR _ _ �_ _ _ _ _ — E Eo 111 31 ]I pl tic F PARTS LIST l � Lieberr POWER IMTEAKLNOTE A EXTENDEDBATTERY _ — CONTROL FABRICATE FROM THE MATERAL SPECIFIED N > NFINITY UPS AND A CABINET / I ACCORDANCE NTH THE CURRENT MAINTENANCE BYPASS / I srroT LEBERVASE SEUREDOECF(CATIONOtAS WITHOUT LINE DIAGRAM (OPTIONAL.) A wl0 OTIERTEN SPEERMSP CMTIONNG SINGLE LINE DUIGRME ®1 E 1 sass I E700360 r 'A. WEBSTER q" 9127101 NONE I ,�T+ =' InM 'i'- RrNroIAEINTERFACE - J � x ots mo T. CHATWIN °•" 3/16/02 ¢ANF BArre ANGUUB *r 1 ®"A. WEBSTER °" 3/18/02 ec7 01748 11/112 UP 8 7 6 5 Q 4 3 2 1 [I Amazon.com: CyberPower Smart App Online OL10000RT3UTF - UP... Your Business: City of Ocoee amazonbusiness Electronics 9 kW UPS http://www.amazon.com/CyberPower-Smart-App-Online-OLIOOOO... ® J.'s Account for Business Wish List Departments Sell on Amazon Business Help BUSINESS SOLUTIONS 'Learn more All Electronics Deals Best Sellers TV & Video Audio & Home Theater Computers Camera & Photo Wearable Technology Car Electronics & GPS Sack to search results for "9 kW UPS' ® CyberPower Smart App Online Share rM 9nnnnDT'2l ITC I IDS - 9 kW - $6,900.74 +Free Shipping . In Stock. Sold by Moon Tech ■ ing 1 -Click ordering is not available for this item. ■ ind sold by Moon Tech 29 when you choose Ship to: J. Allison Butler- OCOEE e Output: 120VI Voltage Add to Wish List a / Form Factor: )epth: 15.75 Inch) Height: -kj Header/ Model: ad (W): 9 KWI Power Have one to sell? Sell on Amazon i Type: UPS Battery) lattery Capacity: 9 Ahl I Run Time: 11 min at Sponsored by Other Brands :ontrol Panel,Removable ViewSonic PJD782OHD 1080p 3D Home Theater... ompliant USB Port,Serial (285) MP / HTTP Remote ,pe: 3 years limited >�,- ±err$577.00 Prepare for Storm Season Tool and supplies to weather the storm. Shop Roll over image to zoom in Generators, Backup Power, Emergency Supplies, and more. Special Offers and Product Promotions • Unlimited Cloud Storage: Never run out of space for all your photos, videos, and files with unlimited storage plans from Amazon Cloud Drive. Learn more • Your cost could be $6,830.74 instead of $6,900.74! Get a $70.00 gift card instantly upon approval for the Amazon.com Rewards Visa Card. Apply now. Technical Details Brand Name: CyberPower Systems Model Number: OL10000RT3UTF Item Weight: 492 pounds 1 of 3 7/21/2015 8:03 AM Amazon.com: CyberPower Smart App Online OL10000RT3UTF - UP.. Product Description http: / /www.amazon.com/CyberPower- Smart- App - Online -OL 10000... CyberPower Smart App Online OL1000ORT3UTF - UPS - AC 200 -240 V - 9 kW - 10000 VA 9 Ah - RS -232, USE; - 19 output connector(s) - 9U. The CyberPower Smart App Online OLIOOOORT3UTF rack/tower uninterruptible power supply (UPS) with Step -down Transformer, LCD Control Panel, and pure sine wave output safeguards mission - critical servers, data center and telecom equipment, VoIP, and internetworking hardware that require seamless power correction. Its Online Double Conversion topology is generator compatible and delivers consistent and clean standard 120V or 200 -240V AC power with zero transfer time to protect connected equipment and prevent costly business interruptions. Auto- bypass insures connected equipment continues to operate seamlessly when an overload or internal fault is detected. The LCD Control Panel provides 38 different settings to check status and customize the operating settings for the OL1000ORT3UTF, plus it can be removed and mounted separately from the UPS for ease of use regardless of where the UPS is installed. Functions include menus for checking power status on 16 different parameters, 19 settings for setup, control, and testing of the UPS, and 3 selections for event logging. With a Product Details Item Weight: 492 pounds Shipping Weight: 492 pounds (View shipping rates and policies) ASIN:BOOP9G3AU2 Item model number: OL1000ORT3UTF Average Customer Review: Be the first to review this item Product Warranty: For warranty information about this product, please click here Date first available at Amazon.com: November 5, 2014 Would you like to update product info, give feedback on images, or tell us about a lower price? Customer Questions & Answers Have a question? Ask the owners here Typical questions asked about products: Is the item durable? Is this item easy to use? What are the dimensions of this item? Customer Reviews There are no customer reviews yet. 5 star Share your thoughts with other customers 4 star 3 star 2 star 1 star Ad feedback ':-.' Customers Viewing This Page May Be Interested In These Sponsored Links (what'sths?) UPS Service & Parts gJ www.millenniumups.com/ - Eaton Mitsubishi APC /MGE Liebert GE 1 Yr Warranty Call Now For A Quote! Power Backups from $25 rF www.upsforiess.com/ - Save up to 90% on major brand Battery backups/UPS's. Go Straight to the Source [T www.egreeneonline.com/ - Manufacturer of Bank & CU Supplies Small Orders, Custom Imprints! Your Recently Viewed Items and Featured Recommendations Inspired by your browsing history Page 1 of 6 2 of 3 7/21/2015 8:03 AM Liebert Innovative Support Systems, Inc. 1030 Sunshine Lane, Suite 1000 Altamonte Springs, FL 32714 FAX: (407) 682 -0024 PH: (407) 682 -7570 COMPANY: PRESIDIO NETWORKED SOLUTIONS ATTN: FAX: FROM: SEAN DEVANEY PROJECT: CITY OF OCOEE - DATACENTER UPS EMERSON - PROPOSALM PAGES DATE: Q02333887 153625LABSD 4 Jul 21, 2015 We are pleased to provide our quotation for the following Liebert / Emerson Network Power system for your consideration on this project. One (1) 3 Ton Nominal Capacity 208/230 -1 -60 Volt Evaporator(s), DataMate Model DME037E -PH7. • Includes evaporator coil, filter drier, thermal expansion valve, R -407C refrigerant unit charge and quick - connect female couplings on both the suction and liquid lines. • Electric Reheat • Steam Canister Humidifier One (1) Liebert Model PFH037A -PL7 208/230/1 Outdoor Condensing Unit. • R -407C refrigerant unit charge • Designed for outdoor ambient of 95 °F. Ship Loose Items: • 1 Sweat Adapter Kit (3 Ton) Services Included: • 1 Year PARTS ONLY Warranty • 2nd Through 5th Year COMPRESSOR ONLY Warranty Included Terms & Conditions: - Quotation Valid for 45 days - Terms are Net 30 Days, subject to manufacturer's approval - Liebert standard Terms & Conditions apply - Please address Purchase Orders to: Innovative Support Systems, Inc. 1030 Sunshine Lane, Suite 1000 Altamonte Springs, FL 32714 Net Price, FOB FACTORY, Freight Included, Less Tax $ 7.710.00 ADD for Field Installed Condensate Pump, if required $ 315.00 ADD for Factory Authorized Warranty Inspection /Start Up $ 500.00 ALL ASPECTS OF INSTALLATION TO BE PROVIDED BY OTHERS SEAN DEVANEY Account Representative 7/22/2015 Liebert- Proprietary Page 1 of 4 LIMITED WARRANTY FOR THERMAL MANAGEMENT PRODUCTS This Warranty is given ONLY to purchasers who buy for commercial or industrial use in the ordinary course of each purchaser's business. General: Liebert Corporation products and systems are in our opinion the finest available. We take pride in our products and are pleased that you have chosen them. Under certain circumstances we offer with our products the following One Year Limited Warranty Against Defects in Material and Workmanship. Please read your Warranty carefully. This Warranty sets forth our responsibilities in the unlikely event of defect and tells you how to obtain performance under this Warranty. ONE YEAR LIMITED WARRANTY AGAINST DEFECTS IN MATERIAL AND WORKMANSHIP PRODUCTS COVERED: This warranty applies to all Liebert branded Precision Cooling products, included but not limited to, unless specifically noted, Liebert Mini- Mate2TM, Liebert DataMatcTm, Liebert ChallengerTM 3000, Liebert Challengefm ITR, Liebert Industrial Cooling Series, Liebert Condenser, Liebert MC, Liebert Drycooler, Liebert DSTM, Liebert DSE, Liebert CWTM, Liebert CRVTM, Liebert InteleCool2®, Liebert XDTM, Liebert DCW, Liebert CWC, Liebert DSC, Liebert EVI, Liebert EVD, Liebert HPC Terms of Warrantv: As provided herein, the Liebert product is warranted to be free of defects in material and workmanship for a period of one year from the start-up date provided the product Warranty Inspection sheet is returned to Liebert, start-up occurs within six (6) months of the Liebert shipping date, and the product has been stored in a suitable environment prior to start-up. The start-up date will be determined only from the completed inspection and start-up sheet received with the product. If the product start-up sheet is not returned to Liebert, the Liebert product is warranted to be free of defects in material and workmanship for a period of thirteen (13) months from date of product shipment by Liebert. The shipment date will be determined only from the Liebert bill of lading. In addition, for products installed in the United States or Canada, the drive package contained in the Liebert DS product and Liebert InteleCool28 Compressor is warranted to be free of defects in material and workmanship for a period of five (5) years from the above referenced dates, as applicable. The drive package contained in the Liebert DS product consists of blower belts, a blower shaft, blower bearings, a blower pulley, and motor sheave. If any part or portion of the Liebert product fails to conform to the Warranty within the Warranty period, Liebert, at its option, will furnish new or factory remanufactured components for repair or replacement of that portion or part, or Liebert may furnish User with a replacement product. Liebert will not assume any labor or shipping charges associated with repair or replacement of the Liebert product or part thereof. This is a Parts Warranty ONLY that does not include Services; all Services shall be provided by a qualified Service provider. Upon Liebert's request this warranty may require recorded proof of Quarterly product maintenance completed by a qualified service provider. If it is determined that failure occurred due to lack of maintenance, Liebert maintains the right to deny the warranty claim. Warrantv Extends to First Purchaser for Use. Non - transferable: This Warranty is extended to the first person, firm, association or corporation for whom the Liebert product specified herein is originally installed for use (the "User ") in the fifty United States or Canada. This Warranty is not transferable or assignable without the prior written permission of Liebert. ASSlgnment of Warranties: Liebert assigns to User any warranties which are made by manufacturers and suppliers of components of, or accessories for, the Liebert product and which are assignable, but Liebert makes NO REPRESENTATIONS as to the effectiveness or extent of such warranties, assumes NO RESPONSIBILITY for any matters which may be warranted by such manufacturers or suppliers and extends no coverage under this Warranty to such components or accessories. Drawings. Descriptions: Precision Cooling Systems Warranty Rev. 9/10/2013 SL-01000 Liebert warrants for the period and on the terms of the Warranty set forth herein that the Liebert product will conform to the descriptions contained in the certified drawings, if any, applicable thereto, Liebert's final invoices, and to applicable Liebert product brochures and manuals current as of the date of product shipment ( "Descriptions "). Liebert does not control the use of any Liebert product. Accordingly, it is understood that the Descriptions are NOT WARRANTIES OF PERFORMANCE and NOT WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE. Warrantv Claims Procedure: Within a reasonable time, but in no case to exceed thirty (30) days, after User's discovery of a defect, User shall contact the local Liebert sales representative from whom the product was purchased. User may contact Liebert at 1 -800 LIEBERT (543 -2378) for local Liebert sales representative information. Subject to the limitations specified herein, the Liebert sales representative will arrange for a Liebert service representative to repair or replace the non - conforming Liebert product warranted hereunder, without charge for materials. User shall bear all labor or shipping charges associated with repair or replacement of the product herein. Warranty coverage will be extended only after the Liebert service representative's inspection discloses the claimed defect and shows no signs of treatment or use that would void the coverage of this Warranty. All defective products and component parts replaced under this warranty become the property of Liebert. Warrantv Performance of Component Manufacturers: It is Liebert's practice, consistent with its desire to remedy Warranty defects in the most prompt and effective manner possible, to cooperate with and utilize the services of component manufacturers and their authorized representatives in the performance of work to correct defects in the product components. Accordingly, Liebert may utilize third parties in the performance of Warranty work, including repair or replacement hereunder, where, in Liebert's opinion, such work can be performed in less time, with less expense, or in closer proximity to the Liebert product. Items Not Covered By Warranty: THIS WARRANTY DOES NOT COVER DAMAGE OR DEFECT CAUSED BY misuse, improper application, wrong or inadequate electrical current or connection, inadequate water or drain services, negligence, inappropriate on site operating conditions, corrosive atmosphere, failure to adequately maintain the Product using a qualified Service provider, repair by non- Liebert designated personnel, accident in transit, tampering, alterations, a change in location or operating use, exposure to the elements, Acts of God, theft or installation contrary to Liebert's recommendations or specifications, or in any event if the Liebert serial number has been altered, defaced, or removed. THIS WARRANTY DOES NOT COVER shipping costs, installation costs, circuit breaker resetting, loss of refrigerant, or maintenance or service items and further, except as may be provided herein, does NOT include labor costs or transportation charges arising from the repair or replacement of the Liebert product or any part thereof or charges to remove or reinstall same at any premises of User. THE PRODUCTS LISTED IN THIS WARRANTY ARE NOT FOR USE IN ANY SAFETY APPLICATIONS OR WITHIN THE CONTAINMENT AREA OF A NUCLEAR FACILITY OR WHERE THE PRODUCTS HAVE POTENTIAL FOR DIRECT PATIENT CONTACT OR WHERE A SIX (6) FOOT CLEARANCE FROM A PATIENT CANNOT BE MAINTAINED AT ALL TIMES. THE PRODUCTS LISTED IN THIS WARRANTY MAY BE PLACED DIRECTLY OVER PATIENTS OR DIAGNOSTIC AND SURGICAL EQUIPMENT ONLY WHERE THE END -USE CUSTOMER HAS SIGNED LIEBERT'S HEALTHCARE APPLICATION SALES AGREEMENT, OTHERWISE THE WARRANTY IS VOID. REPAIR OR REPLACEMENT OF A DEFECTIVE PRODUCT OR PART THEREOF DOES NOT EXTEND THE ORIGINAL WARRANTY PERIOD. Limitations: THIS WARRANTY IS IN LIEU OF AND EXCLUDES ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. USER'S SOLE AND EXCLUSIVE REMEDY IS REPAIR OR REPLACEMENT OF THE LIEBERT PRODUCT AS SET FORTH HEREIN. IF USER'S REMEDY IS DEEMED TO FAIL OF ITS ESSENTIAL PURPOSE BY A COURT OF COMPETENT JURISDICTION, LIEBERT S RESPONSIBILITY FOR PROPERTY LOSS OR DAMAGE SHALL NOT EXCEED THE NET PRODUCT PURCHASE PRICE. Precision Cooling Systems Wa my Rev. 9/10/2013 S1.1O1000 IN NO EVENT SHALL LIEBERT ASSUME ANY LIABILITY FOR INDIRECT, SPECIAL, INCIDENTAL, EXEMPLARY OR CONSEQUENTIAL DAMAGES OF ANY KIND WHATSOEVER, INCLUDING WITHOUT LIMITATION LOST PROFITS, BUSINESS INTERRUPTION OR LOSS OF DATA, WHETHER ANY CLAIM IS BASED UPON THEORIES OF CONTRACT, NEGLIGENCE, STRICT LIABILITY, TORT, OR OTHERWISE. Miscellaneous: NO SALESPERSON, EMPLOYEE OR AGENT OF LIEBERT IS AUTHORIZED TO ADD TO OR VARY THE TERMS OF THIS WARRANTY. Warranty terms may be modified, if at all, only by a writing signed by a Liebert officer. Liebert obligations under this warranty are conditioned upon Liebert timely receipt of full payment of the product purchase price and any other amounts due. Liebert reserves the right to supplement or change the terms of this Warranty in any subsequent warranty offering to User or others. In the event that any provision of this Warranty should be or becomes invalid and/or unenforceable during the warranty period, the remaining terms and provisions shall continue in full force and effect. User shall complete the attached User Information Card and forward it to Liebert within thirty (30) days of receipt of the Liebert product. This Warranty shall be governed by, and construed under, the laws of the State of Ohio, without reference to the conflict of laws provisions thereof. This Warranty represents the entire agreement between Liebert and User with respect to the subject matter herein and supersedes all prior or contemporaneous oral or written communications, representations, understandings or agreements relating to this subject. Precision Cooling Systems Warranty Rev. 9/10/2013 SL -01000 ■ Precision Cooling For Business - Critical ContinuityT" Lieberr DataMate' Economical, Space- Saving Cooling Systems For Sensitive Electronics EMERSON. Precision Cooling Designed To Fit The Smallest Spaces Liebert DataMate precision environmental systems are the perfect solution for cramped quarters requiring temperature and humidity control for sensitive electronics. And while the systems are matched to meet the needs of computers, they are also designed to be convenient for the people sharing space with the protected equipment. Space- saving. The slim, compact Liebert DataMate may be wall- or floor - mounted, and requires minimal service access, limiting floor space requirements. High sensible cooling capacity. Unlike "comfort" air conditioners, Liebert precision cooling systems are designed for the cooling requirements of electronic equipment -80% of the capacity dedicated to the removal of dry "sensible" heat, and 20% for control of humidity. Reliable. The Liebert DataMate installed - base is a testimonial to system reliability. Components include a compressor; a high efficiency copper -tube, aluminum -fin evaporator coil; and a double inlet, direct drive fan. Outdoor Air Cooled. Suitable for roof or ground level site. The condensing unit is designed for operation as low as -30* F. Water/Glycol Cooled Remote. Utilizes an existing water or glycol loop. Condensing unit is located under the raised floor or above the dropped ceiling. u Quiet. The units are designed to operate quietly with the compressor vibration - isolated from the chassis. The cabinet is also insulated to further ensure quiet operation. On many models, the compressor- containing condensing unit can be remotely located to further reduce noise levels in the controlled space. Quiet -Line outdoor condensing units are available for 6 -8 dba sound level reduction over the standard models. Flexibility options. Liebert DataMate 60Hz systems are available in capacities of 1.5, 2 and 3 tons in air, water, glycol, and a self- contained 3 ton chilled water model (3 -Ton models only in 50Hz). Systems may be configured as self - contained or separated from the condensing unit, depending on the model. l J Indoor Air Cooled. For high -rise and other applications where roof or ground level locations are impractical. May be located above the dropped ceiling and ducted to the outside. Designed for operation down to -20'F ambient. WaterlGlycol Cooled Integral. Totally packaged. A single power and water supply connection puts the unit in operation. Easy installation. All Liebert DataMate components are precharged, and require no field brazing, evacuation or charging. Precharged refrigerant lines are available to connect evaporator and remote condensing unit modules when required. Two -speed fan operation. High speed provides quiet operation and maximum cooling. Low speed provides maximum dehumidification and lowest sound level. The speed can be automatically or manually selected. Corrosion - Resistant Cabinet. Durability is ensured with Powder Coated Paint panels. Chilled Water. This unit simply connects to a chilled water loop, for quick and easy installation. Specifications Indoor and outdoor condensing unit options maximize Liebert Data Mate installation options for better system flexibility. Outdoor models are available in Quiet -Line and High Ambient versions. 0 60Hz ' SOHz Air - Cooled System with Outdoor Condensing Unit Split System with Indoor Condensing Unit Split with Outdoor Condensing with Indoor Condensing System Unit Split System Unit Split System Evaporator DME020E DME027E DME031E OME027E DME037E DME037E DME037E Condensing Unit PFH020A PFH027A PFH037A MCD24A I MCD36A PFH036A MCD35A Net Capacity Data' - kW (Btuh) - High Fan Speed Total 5.40 (18,500) I 7.10 (24,200) 10.1 (34,600) 6.85 (23,300) 9.60 (32,700) 9.90 (33,800) 9.45 (32,300) 80 °F DB (26.7 °C) jl 38 %RH Sensible 5.40 (18,500) 7.10 (24,200) 9.70 (33,100) 6.85 (23,300) 9.40 (32,000) 8.85 (30,200) 8.65 (29,500) °C) Total 5.05 (17,200) 6.60 (22,500) 9.75 (33,200) 6.35 (21,700) 9.15 (31,300) 9.55 (32,500) 9.10 (31,100) 75 °F DB (23.9 I 45 %RH Sensible 4.90 (16,700) 6.50 (22,200) 8.60 (29,400) 6.35 (21,600) 8.35 (28,500) 7.90 (26,900) 7.70 (26,300) °C) Total 4.85 (16,500) 6.35 (21,700) 9.50 (32,400) 6.10 (20,800) 8.95 (30,600) 9.30 (31,800) 8.90 (30,400) 1 72 °F DB (22.2 I 50 %RH Sensible 4.50 (15,400) 6.05 (20,600) 7.95 (27,100) 5.90 (20,100) 7.70 (26,200) 7.30 (24,900) 7.10 (24,300) 1 60Hz 50Hz Water Cooled Glycol Cooled Water Coolcd Glycol Cooled Evaporator DME020E DME027E DME037E DME020E DME027E DME037E DME037E DME037E Condensing Unit DMCO22WG I "DMCO29WG) I "DMC040WC DMCO22WG I "DMCO29WG� - DMC040WG/ MCD37W MCD37W MCD26W" MCD38W" MCD26W" MCD38W" Net Capacity Data' - kW (Btuh) - High Fan Speed 80 °F DB (26.7 °C) I Total 5.90 (20,100) 7.95 (27,200) 11.4(38,900) 5.15 (17,600) 6.75 (23,000) 9.65 (32,900) 11.3 (38,700) 9.30 (31,800) 38 %RH Sensible 5.80 (19,800) 7.90 (27,000) 10.3 (35,300) 5.15 (17,600) 6.75 (23,000) 9.40 (32,100) 9.55 (32,600) 8.60 (29,300) I Total 5.50 (18,800) 7.55 (25,800) 11.0 (37,400) 4.80 (16,300) 6.25 (21,300) 9.20 (31,400) 11.0 (37,400) 8.95 (30,500) °F DB (23.9 °C) 175 45 %RH Sensible 5.15 (17,600) 7.10 (24,200) 9.20 (31,400) 4.75 (16,200) 6.25 (21,300) 8.35 (28,500) 8.55 (29,200) 7.60 (26,000) °C) I Total 5.35 (18,100) 7.35 (25,000) 10.7 (36,600) 4.60 (15,700) 6.00 (20,500) 8.95 (30,600) 10.7 (36,600) 8.75 (29,900) 172 °F DB (22.2 50 %RH I Sensible 4.75 (16,200) 6.55 (22,300) 8.55 (29,100) 4.35 (14,900) 5.85 (19,900) 7.70 (26,300) 7.95 (27,200) 7.05 (24,000) 60 Hz I SOHz IEvaporator CHILLED I WATER Condensing Unit I DME044C I DME044C Net Capacity Data" -kW (Btuh) -High Fan Speed 80 °FDB(26.7 °C) I Total 10.5 (36,000) 9.1 (31,100) 38 %RH Sensible 9.65 (32,900) 8.3 (28,200) to i 1 V 4J 75 °FDB(23.9 °C) Total 8.45 (28.900) 7.6 (25,900) iiiililloumiiui '�tllViViuiiiiuhiiliifiiimiiJ' 45 %RH Sensible 7.9s (27,100) 6.8 (23,200) Microprocessor control system. Standard 60Hz units are CSA certified I The microprocessor control system, to the harmonized U.S. and Canadian 72 °FDB (22.2 °C) Total 7.65 (26.100) 6.6 (22,600) with its user - friendly wall -mount display, product safety standard, CSA C22.2 No 50 %RH Sensible 6.90 (23,500) 5.9 (20,200) provides precise temperature and 236JUL 1995 for "Heating and Cooling " The netcapacity data hasfan motor heatfactored in forall ratings accurate alarm setpoints. Using touch- Equipment" and are marked with the CSA and the entering air conditions of 75 °F (23.9 °C), 45 %RH, is the sensitive buttons, the monitor control C - -US logo. standard rating condition forASHRAE 127 -2007. All capacities are panel allows you to select and display nominal values; actual performance will be 15%." time, temperature, humidity, alarm indication and other parameters. 0