HomeMy WebLinkAboutItem #07 Approval to Reallocate Existing Capital Budet Funds of $15,000 to Purchase Power and AC Backup UnitsD
0 C 0 (>- (?
florlda
AGENDA ITEM COVER SHEET
Meeting Date: August 4, 2015
Item # 7
Reviewed By
Contact Name: Al Butler, Support Services Department Director:
Contact Number: 407 - 554 -7063 City Manager:
Subject: Authorization to reallocate existing capital budget funds of $15,000
backup units for the City Hall Server Room at a total cost of $11,791.80
modifications to install and use these units.
and to make internal
Background Summary:
The FY 2015 Budget established a capital construction project to install a fire suppression system in the
City Hall Server Room at a cost of $15,000. This budget level was based on a price quote secured by
staff at the time the budget item was proposed. When this project was actually put out for bids, the only
offer was at a cost of $32,000 —an amount that cannot be justified given the construction of a backup
data center at Police Headquarters that would allow us to recover critical operations and data in case of
a fire at City Hall.
With the original intent not being feasible, staff seeks to address the next critical need for the City Hall
Server Room, which is to provide power backup and a standby air conditioning unit. During the past
year, both power interruptions and one air conditioner unit failure have occurred, with the result that
critical servers lost power or overheated and shut themselves off. The power issue is caused by the
Server Room not being completely on generator backup circuits. The existing group of small battery
backups (aka, uninterruptible power supply or UPS) is capable of extending operations for only about 30
minutes and not all systems can be accommodated. The power capacity of existing generator- supported
circuits is not adequate to support the total power demand, which will only increase as additional storage
units are put into operation. The air conditioning unit in the room is barely adequate to meet existing
needs and the room heats up quickly when the AC unit stops running.
Staff investigated the marketplace for both large- capacity UPS products and portable cooling units. Of
the many options available, three UPS units and two AC units were selected for additional analysis.
Based on performance and pricing, staff selected the TX90 10 kVA UPS and CoolCube 12 cooling unit,
both from Xtreme Power Conversion. In addition to providing the best performance, these were also the
lowest cost products in each category. Other products considered were the Liebert APS 10 kVA UPS
from Presidio, the CyberPower Smart App Online OL10000RT3UTF from Moon Tech (via Amazon), and
the Liebert PFH037A -PL7 outdoor condensing unit paired with the DataMate DME037E -PH7 from
Innovative Support Systems, Inc. Staff also considered installing a 3 -ton Panasonic wall- mounted unit at
a cost of about $7,000.
Along with the UPS, staff recommends that a four - module UPS parallel bypass switch be used to allow
future expansion of the installation as power needs grow. Both the UPS and the AC unit can be readily
moved to another location. Some re- wiring will be required to integrate the UPS into the building's power
system. Working with the city's Public Works Department, circuits connected to the existing backup
generator will be extended to the Server Room and connected to the input ports on the UPS. A
secondary panel will be used in the room to provide UPS - filtered power to all outlets and to the backup
AC unit. (The existing AC unit is already on a generator circuit.) The standby cooling unit includes
accessories to allow automatic start-up and to exhaust hot air into the plenum space above the
suspended ceiling. The UPS will bridge the time period for generator start-up during power failures.
Issue:
The city needs to acquire a UPS capable of providing backup power and a standby /supplemental cooling
unit for the entire City Hall Server Room.
Recommendations
Staff recommends that the City Commission authorize the purchase of an Xtreme Power Conversion
TX90 10 kVA/9 kW scalable online isolated UPS with four -unit parallel tie panel at a cost of $6,946.80
and an Xtreme Power Conversion CoolCube 12 cooling unit with accessories at a cost of $4,845.00, both
from Creative Power Solutions. The portability of the CoolCube 12 unit adds to its value, as it can be
used in multiple locations. The balance of the original project budget of $15,000 would be used to pay
the costs of making changes to the City Hall power system to make the greatest possible use of the UPS
and to supply conditioned backup power to all outlets in the Server Room.
Attachments:
Price quotes from Creative Power Solutions, Presidio, Moon Tech (via Amazon), and Innovative Support
Systems, Inc., along with descriptive materials on each unit examined by staff.
Financial Impact:
This procurement has no impact on the adopted budget except to change the purpose for which the
funds are to be expended. The cost will be covered by the existing Support Services Capital
Improvements budget line item (Account No. 001 - 518 -00- 6302), which may need to be allocated to
various accounts depending on the specific goods and services to be acquired. Any additional funds
needed to complete the project will come from existing budget sources in Cost Centers 516 and /or 518.
Type of Item: (please mark with an 'Y)
Public Hearing
For Clerk's Dent Use:
Ordinance First Reading
Consent Agenda
Ordinance Second Reading
Public Hearing
Resolution
Regular Agenda
X Commission Approval
Discussion & Direction
Original Document/Contract Attached for Execution by City Clerk
Reviewed by N/A
Reviewed by City Attorney N/A
Reviewed by Finance Dept.) N/A
2
CREATIVE
POWER
'MBSOLUTIONS
Name /Address
PO Box 1015
Groveland, FL 34736
352 - 429 -5086
352 - 255 -1496
City of Ocoee
Attention: Jack Butler
150 N Lakeshore Dr
Ocoee, FL 34761
Date Estimate No. Project
07/23/15 6501 �uote TX90 an...
Item Description
UPS Xtreme Power TX90 Series 10kVA/9kW Scalable
Isolated Online UPS. System includes (1) TX90 -10k
UPS module and Four Module Parallel Tie Panel.
System is Scalable to 30kVA/27kW N +1 or
40kVA/36kW Capacity. Parallel Tie panel includes
(4) 60A UPS Module Output Breakers and 200A
System Maintenance Bypass Switch (Break Before
Make). TX90 UPS Modules each include Internal 4
minutes Battery, Output Isolation Transformer,
Internal Maintenance Bypass Switch (Make Before
Break), Parallel Cable, two Communication Slots,
Shutdown Software, Communication Cables,
Emergency Power Off (EPO) and Casters. Voltage
shall be 20OV -240V nominal input and 240/120V
Split Phase (3 -wire plus ground) output. Selectable
output voltages are 100V, 110V, 115V, 120V, 200V,
208V, 220V, 230V, 240V. 208/120V is available with
120V and 88V legs. Optional Load Breakers are
available. TX90 Series be programmed as 50 -60HZ
or 60 -50Hz Frequency Converter. Factory Trained
onsite 5x8 Start -up is included (most USA
locations). UL/FCC Approved; 3 -Year Full Warranty;
UPS Module Dimensions: (1) 11.4 "W x 25.4 "D x
29.5 "H, (1) 340 lbs. Wall mount Parallel Tie Panel:
15.5 "W x 4.5 "D x 40.5 "H, 50 Ibs
Quote valid fo 30 days.
Page 1
Estimate
Quantity Cost I Total
1 1
1 6,946.80 6,946.80
Total
Estimate
CREATIVE PO Box 1015
POWER Groveland, FL 34736
352 - 429 -5086
SOLUTIONS04C" 352- 255 -1496
Name /Address
City of Ocoee
Attention: Jack Butler
150 N Lakeshore Dr
Ocoee, FL 34761
Date Estimate No. Project
07/23/15 6501 Quote TX90 an...
l
Item Description Quantity Cost Total
Part Internal SNMP/WEB Card for use with T90 and TX90 1 177.00 177.00
Series UPS; Allows for monitoring and management
of UPS through a web browser or SNMP platform:
Provides shutdown of remote clients via LAN, and
Email Notification of UPS status and events.
packaging = 5.7 "W x 5.2 "D x 1.7 "H, 0.3lbs
air conditioning With a revolutionary modular design that easily 1 3,000.00 3,000.00
unit adapts to virtually any application, MaxPower's
CoolCube 12 is the only air conditioning solution in
the industry that changes to fit your individual
needs. The compact, 12,000 Btu /h module can be
rack - mounted, hung from the ceiling, stacked for
capacity or redundancy, or used as a stand -alone
portable unit - simply by adding the respective
accessory
Contents:
(1) CoolCube 12 Module, (1) Remote Control, (1)
Unpacking Instructions Sheet, (1) Warranty
Registration Card, (1) Operation Manual
Part The CVK -8 is the field installed ceiling panel 1 180.00 180.00
conversion kit that converts the CK -8 into a
two -duct ceiling panel, for both discharge and
intake of condenser air above a drop ceiling. The kit
is to be used in conjunction with the CCP -8
Quote valid fo 30 days. Total
rl„nto lin ;A f— Qn .4-
Page 2
Estimate
CREATIVE PO Box 1015
POWER Groveland, FL 34736
352 - 429 -5086
SOLUTIONSO(" 352- 255 -1496
Name /Address
City of Ocoee
Attention: Jack Butler
150 N Lakeshore Dr
Ocoee, FL 34761
Date Estimate No. Project
07/23/15 6501 Quote TX90 an...
Item Description Quantity Cost Total
Condenser Return Air Plenum.
Contents:
(1) Discharge Baffle
(1) 8 -inch Diameter Flex Duct, 120" Length
(1) 8 inch Duct Flange
(1) Duct Strap, 48"
(4) #8 Thread Forming Screws
* Duct flange comes pre - installed onto duct flange.
Part The CCP -8 is the field installed condenser plenum 1 192.00 192.00
kit that allows for the ducted return of air to the
condenser. The plenum has a filter rail, and is
equipped with an 8 -inch duct round flange.
Contents:
(1) Condenser Plenum
(1) 12/20 filter
Part The CPC -1 is the field installed condensate pump 1 156.00 156.00
kit that allows for the collection and pumping of
condensate from the CAC1211. The pump is
capable of a 20 foot lift, and installs in the unit, in
place of the condensate bucket.
Contents:
(1) 120V condensate Pump (with mounting bracket
attached)
(1) 5/8 -inch Corrugated Drain Hose
Quote valid fo 30 days. Total
(l inic v�lirl fnr Q(1 rlovc
Page 3
Date Estimate No. Project
07/23/15 6501 �uote TX90 an...
Item
Part
Part
Start Up
Description
(1) 3/8 -inch x 25 ft condensate line
(2) Hose clamps
(1) 1 -1/8 -inch Spider bushing
(1) 3/4-inch bushing
(2) Sheet Metal Screws
Remote Thermostat Kit
'Display Cable Sold Separately.
Remote Display Cable 25ft for Cool Cube 12
UPS Start-up
Normal Business Hours: 8:00am- 5:00pm
Exempt
Quote valid fo 30 days.
('li infc inaHrl fnr 4(1 r —
Page 4
Quantity
Estimate
Cost
1 150.00
1 30.00
960.00
0.00%
Total
Total
150.00
30.00
960.00
0.00
$11,791.80
PO Box 1015
CREATIVE
Groveland, FL 34736
CPOWER
352 - 429 -5086
S OLUTIONSOOI "
352- 255 -1496
Name /Address
City of Ocoee
Attention: Jack Butler
150 N Lakeshore Dr
Ocoee, FL 34761
Date Estimate No. Project
07/23/15 6501 �uote TX90 an...
Item
Part
Part
Start Up
Description
(1) 3/8 -inch x 25 ft condensate line
(2) Hose clamps
(1) 1 -1/8 -inch Spider bushing
(1) 3/4-inch bushing
(2) Sheet Metal Screws
Remote Thermostat Kit
'Display Cable Sold Separately.
Remote Display Cable 25ft for Cool Cube 12
UPS Start-up
Normal Business Hours: 8:00am- 5:00pm
Exempt
Quote valid fo 30 days.
('li infc inaHrl fnr 4(1 r —
Page 4
Quantity
Estimate
Cost
1 150.00
1 30.00
960.00
0.00%
Total
Total
150.00
30.00
960.00
0.00
$11,791.80
XTREME POWER CONVERSION TX90 /T90 6kVA to 40kVA
Parallel Scalable System
Online scalable UPS for high
power and critical N +1 redundant
applications
Xtreme TX90 and T90 parallel N +1 redundant online
Uninterruptible Power Supply (UPS) provides the ideal
solution for the most demanding critical power re-
quirements. Configurations up to 40kVA can easily be
configured using individual RVA or 10kVA modules.
Xtreme N +1 configurations allow complete serviceabil-
ity and redundancy. Should an individual UPS require
maintenance, the UPS is automatically taken offline.
A notification is provided to the user from the LCD
display and an audible alarm. The failed UPS module
may be serviced or replaced without the remaining
UPS modules or connected load having to be powered
down.
For single module RVA & 10kVA
systems, reference the TX90 /T90 at:
www.xpcc.com /t6 -10
PRODUCT SNAPSHOT
> Redundant and scalable UPS with an output up to 40kVA
> Galvanic isolated systems (TX90) provide full electrical noise
isolation and 120/240V split -phase output
> Transformerless systems (T90) provide the most economical
solution for 200V, 208V, 220V, 230V, and 240V applications
> Optional extended battery banks & chargers
FEATURES
0.9 output power factor —
more wattage for high density
loads
Galvanic isolation transformer
(TX90)— eliminates common
mode noise and provides
power conditioning during nor-
mal and bypass operation
200 amp parallel tie panel —
provides parallel tie and
system maintenance bypass
for up to four T90/TX90 power
modules.
Lockable casters— simplify
installation and maintenance
Hot swappable internal
battery trays —UPS module
batteries are easy to replace
without interrupting the load
UPS module bypass —
allows individual module
repair with internal mainte-
nance bypass
Extended battery runtimes —
optional external battery
cabinets and chargers can be
added for extended runtime
applications.
MODEL SELECTION GUIDE
OUTPUT
Capacity
Capacity (redundant)
Voltage
Scalable
Voltage
BATTERY Battery runtime (internal)
PHYSICAL UPS dimensions (W x D x H)
Number of UPS modules
Optional external battery cabinets
Tie panel dimensions (W x D x H)
APPROVALS
SYSTEM INCLUDES
6kVA (5.4kW) 12kVA (10.8kW) 18kVA (16.2kW) 24kVA (21.6kW)
N/A 6kVA (5.4kW) N +1 12kVA (10.8kW) N +1 18kVA (16.2kW) N +1
208VAC or 240VAC
All models are scalable to 24kVA or 18kVA N +1
TX90: 240/120VAC or 100, 110, 115, 120, 200, 208, 220, 230, 240VAC selectable*
T90: 208VAC or 200, 220, 230, 240VAC selectable
6 minutes at 100% load / 17 minutes at 50% load
11.4 x 25.4 x 29.5 in
1 2 3 4
11.4 x 25.4 x 29.5 in (EBP960, EBP940, EBP920)
15.5x4.5x40.5in
UL1778, cUL, CE, FCC A
UPS modules with internal batteries, 200A parallel tie panel with 40A module
output breakers, parallel communication cables.
INPUT
Capacity
10kVA (9kW) i 20kVA (18kW) 30kVA (27kW) 40kVA (36kW) **
UPS module
Capacity (redundant)
N/A 10kVA (9kW) N +1 20kVA (18kW) N +1 30kVA (27kW) N +1
Voltage
208VAC or 240VAC
TX90 or T90
Scalable
All models are scalable to 40kVA or 30kVA N +1
OUTPUT
Voltage I
TX90: 240/120VAC or 100, 110, 115, 120, 200, 208, 220, 230, 240VAC selectable*
UPS module
90/T90 parallel sy: > -a_rn
T90: 208VAC or 200, 220, 230, 240VAC selectable
BATTERY
Battery runtime (internal)
4 minutes at 100% load / 12 minutes at 50% load
PHYSICAL
UPS dimensions (W x D x H)
11.4 x 25.4 x 29.5 in (T90) 11.4 x 25.4 x 34.7 in (TX90)
Number of UPS modules
1 2 3 4
Optional external battery cabinets
11.4 x 25.4 x 29.5 in (EBP960, EBP940, EBP920) _
Tie panel dimensions (W x D x H)
15.5 x 4.5 x 40.5 in
APPROVALS
UL1778, cUL, CE, FCC A
SYSTEM INCLUDES
I
UPS modules with internal batteries, 200A parallel tie panel with 60A module
output breakers, parallel communication cables.
'2401120V Spht Phase (3 wire plus ground) a default output. Selectable
voltages: 100V, 110V, 115V, 120V, 2001, 208V . 230V,, 240V. Two low voitoo ° »er tops moy be connected
in parallel to provide a single full copocity 100V, 110V, 115V, 120V output. 208112OV is available with 88V leg. Please speolIy
* *Xtreme parallel tie panel is limited to 160A.
Utility input feed
Utility Input Panel
(provided by others)
_..
TX90 or T90
UPS module
_..
TX90 or T90
UPS module
TX90 or T90
UPS module
TX90 or T90
UPS module
90/T90 parallel sy: > -a_rn
diagram
Xtreme Power 200A
Parallel Tie Panel
Module output breakers
10kVA:60A
6kVA: 40A
Maintenance bypass
breaker 200A
TX90: break - before -make
T90: make - before -break
Output to critical loads
Load breakers are optional
TX90: 240/120V* (L.i, Lz, N, G)
T90: 208 or 240V (Li, Lz, G)
XTREME POWER CONVERSION COOLCUBE 12 For more information, visit www.xpcc.com /ccl2
Cooling for Critical Electronics
Modular air conditioning for critical
electronics
The CoolCube 12 is the only air conditioning solution in
the industry that changes to fit your individual needs.
With it's revolutionary modular design the CoolCube 12
easily adapts to virtually any application. The CoolCube
12's modularity gives it the ability to efficiently cool hot
spots at their source making it the number one choice for
IT environments.
Whether your telecommunications room is a converted
coat closet or a mechanical room, the versatile Cool-
Cube 12 is ideal for any location, easily fitting into the
infrastructure of any building. The CoolCube 12 protects
expensive IT investments from overheating. Studies have
shown every 10°C rise in nominal temperatures results in
a 50% reduction in the lifetime and long term reliability
of IT hardware. The CoolCube 12 operates down to 65 °F,
creating the perfect environment for your IT equipment.
PRODUCT SNAPSHOT
> Available model: 12,000 BTU /H
> 5 year compressor warranty
> Draws less than 10 amps in most applications
> Provide cost effective, efficient, and mobile cooling
> Standard with handle kit and casters
> UL, cUL listed
FEATURES
Modularity — CoolCube 12 can
be rack mounted, hung from
the ceiling, stacked for capacity
or redundancy, or stand -alone
portable unit
Compact 13U module —fits
into an open 2 -post or 4 -post
19" rack, occupying just 13U of
rack space
Commercial grade —steel
construction with heavy duty
oversized casters
Compact design — CoolCube 12
is 50% smaller than competitors
Condensate pump — optional
condensate pump kit installs
in moments with quick plug
connection
Automatic restart —unit re-
starts automatically when power
is reapplied after an outage
R410A refrigerant -earth
friendly refrigerant does not
deplete the Ozone like R22
MODEL SELECTION GUIDE
COOLING Cooling capacity
Air flow (high /low) evaporator
Air flow condenser
Refrigerant
ELECTRICAL Power supply voltage
Power supply frequency
Current consumption
Circuit breaker size
Power consumption
NEMA plug
For more information, visit www.xpcc.com /cc12
12,000 BTU /H
400 /320 CFM
490 CFM
R410A
115VAC
60Hz
12A
15A
1180W
5 -15P
10 ft
Unit automatically restarts when power is reapplied after outage
17.3 x 24.0 x 20.0 in
133lbs
65- 105 °F
8 in
2 gal
UL, cUL
1 year system (USA), 5 year compressor warranty
Auto restart - CoolCube 12 will restart to the last set
point automatically when power is reapplied after
an outage
Fan speed - In AUTO mode, the evaporator blower
will adjust air flow automatically for added comfort
and performance. In MANUAL mode and the evapo-
rator blower will run continuously at one of six levels
of fan speed.
Moisture control - The system operates in the cool-
ing mode to reduce humidity within the conditioned
space.
Power cord length
Automatic restart
PHYSICAL
Dimensions (W x D x H)
Weight
Operating conditions
Hot air duct diameter
Condensate tank capacity
APPROVALS
WARRANTY
COOLCUBE 12 ACCESSORIES
Model
Description
CK -8
8 in ceiling discharge kit
CVK -8
Ceiling panel conversion kit
CPC -1
115V condensate pump kit
CNK -1
2 in x4 in nozzle kit
CDA-8
8 in discharge adapter
CEP-6
2 in x 6 in evaporator return plenum
CCP-8
8 in condensate return plenum
CFK -1
Feet kit
CRD -1
Rack diffuser
SK -1
Stacking kit
RCK-1
19 in rack installation kit
RTK -1
Remote thermostat kit
012 -009
Remote display cable, 25 ft
012 -010
Remote display cable, 50 ft
012 -008
Remote display cable, 75 ft
012 -020
Remote temp sensor, 25 ft
For more information, visit www.xpcc.com /cc12
12,000 BTU /H
400 /320 CFM
490 CFM
R410A
115VAC
60Hz
12A
15A
1180W
5 -15P
10 ft
Unit automatically restarts when power is reapplied after outage
17.3 x 24.0 x 20.0 in
133lbs
65- 105 °F
8 in
2 gal
UL, cUL
1 year system (USA), 5 year compressor warranty
Auto restart - CoolCube 12 will restart to the last set
point automatically when power is reapplied after
an outage
Fan speed - In AUTO mode, the evaporator blower
will adjust air flow automatically for added comfort
and performance. In MANUAL mode and the evapo-
rator blower will run continuously at one of six levels
of fan speed.
Moisture control - The system operates in the cool-
ing mode to reduce humidity within the conditioned
space.
PRESID10
City of Ocoee
FROM: Presidio Networked Solutions
Accounts Payable
QUOTE:
20015115003147 -01
150 N. Lakeshore Drive
5337 Millenia Lakes Blvd.
Ocoee, FL 00000
Suite 300
DATE
PAGE
07/20/201
1 of 2
TO:
City of Ocoee
FROM: Presidio Networked Solutions
Accounts Payable
Susan Bacci
150 N. Lakeshore Drive
5337 Millenia Lakes Blvd.
Ocoee, FL 00000
Suite 300
Orlando, FL 32839
(p) (407) 905 -3100 Ext. 1523
sbacci @presidio.com
(p) 407.641.0563
Customer#: CITY0262
Account Manager: Ross LoBrutto
Inside Sales Rep: Susan Bacci
Title: City of Ocoee - 101kVA
Description Unit Price City Ext Price
1 10kVA APS Single Phase One (1) Liebert APS UPS System rated at 10 kVA/9.0 kW with 5 minutes backup time. $9,061.10 1 $9,061.10
UPS Model AS5BONCVGNNX887, single phase 120/208 input and output, with the following
features:
Comments: On -line double conversion design with a sine wave output
N +x parallel redundancy to provide a fault tolerant network of power protection for continuous systems availability
Quoted model is configured Non - redundant
Input and output noise suppression
Main input, output, and internal maintenance breaker
Input power factor 0.99
6 hour battery recharge time to 90% capacity
Fault tolerant microprocessor -based control and monitoring
Low voltage distortion output inverter
Flame- retardant, Sealed valve regulated batteries
LCD display module with mimic diagram of power flow and provides digital metering, event logging, user customize -able set
points (low battery alarm, battery test, auto - restart delay, display language)
All modules are hot - swappable to provide maximum system flexibility and availability
Casters and leveling feet
WEEE, REACH, and RoHS (6 by 6) compliant
Integral output distribution providing None outlets
Integral output distribution providing None outlets
* Units are capable of rack mounting with optional rack mounting kit
* UPS frame is designed for maximum of 15 kVA, 208/12OV, 60 Hz, L- L -N -PE
UL 1778 4th Edition, c -UL, Listed
(1) IntelliSlot Velocity /Life.Net Card; P /N: IS- UNITY -DP; Offers a web interface to monitor and configure the Life.nel and
Emerson Network Power proprietary protocols for use with the Emerson Life Station, Liebert Worm and Emerson Trellis. It
allows you to select and configure two of the available third party protocols — SNMP, Modbus or BACnet for interfacing to
Building Management Systems.
UPS System Services Include:
Start-up service includes one site trip by a Liebert Services customer engineer after the unit has been installed. The site trip
includes the following services for each system: non - powered inspection, unit electrical and operational checkout, full parts and
labor for any work required on the unit, and basic customer operation training. Start-up also provides the customer with a
guaranteed 6 hour on -site response for emergency service and includes onsite labor, parts, and travel for the full two-year
warranty period.
Warranty Inspection Start-Up to be provided between the hours 0800 and 1700 Monday to Friday, business days
Sub Total: $9,061.10
Grand Total: $9,061.10
QUOTE: 20015115003147 -01
PRESID10.
PAGE: 2 of 2
Quote valid for 30 days from date shown above. Prices may NOT include all applicable taxes and shipping charges. All prices subject to change without notice. Supply subject to
availability.
This quotation subject to Presidio Standard Terms and Conditions as follows
Credit: Net 30 Days (all credit terms subject to prior Presidio credit department approval)
The price included herein reflects a 3% discount for payment by cash, check or wire transfer. This discount will not apply in the event that customer pays using a credit card or debit
card.
Delivery: FOB origin (FOB destination (CONUS) applicable to Federal Government Customers only) Orders shipped from a manufacturer to Presidio at customer request for
warehousing, configuration, storage or otherwise, shall be deemed to have been shipped to customer FOB origin.
Changes to the above Terms and Conditions must be accepted in writing by Presidio Networked Solutions
Preprinted terms appearing on Customer Purchase Orders must be accepted in writing by Presidio Networked Solutions to be applicable.
Size Business: Large, CAGE Code: 0K1)05; DUNS 15- 405 -0959, CEC: 15- 506005G; Tax ID# 58- 1667655
Product is warranted by the Manufacturer, not by Presidio Networked Solutions. Please consult Manufacturer for warranty terms.
Opened product is non - returnable. Unopened equipment is non - returnable after 30 days from shipment date. Presidio reserves the right to deny RMA requests in the event the
Manufacturer will not provide for an authorized return. If integration of product is performed at a Presidio facility, transfer of ownership occurs as of inception of integration regardless of
shipment terms as manufacturers will not accept return of open product.
Please inspect equipment thoroughly against packing list before opening.
Pricing for Professional Services are best -effort estimates only. Actual pricing will be finalized as part of a mutually-agreeable Statement of Work.
Import Clearance and Documentation - Customer shall be responsible for the Customs clearance process, where applicable, and for obtaining any and all required license and permits as
well as satisfying any formalities required to import the Products into the Territory in accordance with all applicable laws and regulations, including but not limited to the payment of duties,
taxes, surcharges, fees and any special assessments and take all other actions required in connection with the importation and Customs clearance of Products. Customer shall be
responsible for ensuring documentation necessary for the import and Customs clearance process and recordkeeping meets all applicable laws and regulations.
Export Controls - (i) Customer shall comply with all applicable Export Control Laws, including but not limited to the U.S. Department of Commerce's Export Administration Regulations, in
the performance of this Agreement and in the import, export, re-export, shipment, transfer, use, operation, maintenance, repair or disposal of Products and any related parts, components,
accessories, know -how or technology. 'Export Control Laws' means all export control, economic sanction and antiboycott laws and regulations of the United States and other jurisdictions,
including but not limited to the U.S. Export Administration Regulations, the U.S. International Traffic in Arms Regulations and the U.S. Department of Treasury's economic sanctions
regulations. (ii) Product and any related parts, components, accessories, know4ww and technology must not be re-exported or transferred to restricted persons and sanctioned countries
designated by the U.S. Government, including Cuba, Iran, North Korea, Sudan and Syria, unless authorized in advance by the Company and the U.S. Government. (iii) Customer
acknowledge that transfers of Product and any related parts, components, accessories, know -how and technology may be subject to the terms and conditions of an export license, license
exception or other authorization pursuant to Export Control Laws. Customer agree to comply fully with the terms of any licenses, license exceptions or authorizations and to provide
Presidio Networked Solutions access to records needed to confirm such compliance upon request. (iv) Customer further acknowledges that certain Products may contain encryption and
may be restricted for export, re-export, shipment or transfer to government end users in certain countries.
Customer hereby authorizes and agrees to make timely payment for products delivered and services
rendered, including payments for partial shipments
Customer Signature Date
Liebert APS UPS Liebert EBC Liebert APS
16 Bay 14 Bay Single Phase UPS
XFMR Free External Battery Cabinet 15kVA/13.5kW
Liebert 28 minute Battery Run Time
APS ® • 208/120 volt, 2 phase
MBC • ••••• •
5kVA/4.5kW 5kVA/4.5kW
Power Module Power Module Battery Module Battery Module
#t #2 #1A #'IB Liebert 15kVA APS UPS:
Dimensions: 17.3 "W x 33.5"D x 38.1 "H
5kVA/4.5kW Spare Slot for Weight: 740 Lbs.
Power Module Power Module Battery Module Battery Module Service Clearance: 39" in Front, 12" in Rear
#3 #4 #2A #26
Heat Output: 6,768 BTU /hr
Battery Module Battery Module Battery Module Battery Module
#1A #1B #3A #3B Liebert EBC (External Battery Cabinet):
I
Dimensions: 17.3 "W x 28 "D x 381 "H
Battery Module Battery Module Battery Module Battery Module
Weight: 735 Lbs.
#2A #26 #4A #4g
Liebert APS Maintenance Bvpass Cabinet:
Battery Module Battery Module Battery Module Battery Module Dimensions: 9.5 "W x 26.5 "D x 30.5 "H Wei ht: 85 Lbs.
#3A #3B #5A I #5B I g
Battery Module Battery Module
#9 11 #4B
Battery Module Battery Module
V I I #5B
Battery Module Battery Module
#6A I I #6B
Battery Module Battery Module
#7A I I #7B
Battery I � Battery Bodule I 1
s slls
9.5" 17.3" ��
sl
17.3 hLiebert
'Masan C Rk.f P.— 6 Cooling T- hnobgiss'
Innovative Support Systems, Inc.
Project: Liebert 15kVA APS Single Phase UPS System
s
EMERSON.. Title: Cabinet Data, APS 16 Bay TX -Less Cabinet, 15kVA/13.5kW
NeUvork Povier Date: 06- 24/2014 1 By: Sean Devaney I Drg# - Ocoee -
MANUAL
BYPASS
INPUT OUTPUT
L —L —N —G L —L —N —G
(50/60Hz) EMI POWER EMI OUTPUT AND (50 /6OHz)
FILTER MODULE(s) FILTER BYPASS
CONTACTOR
BATTERY
MODULE(s)
DRAWN BY SHEET NO.
K. STACY 1 OF 1 ONE -LINE DIAGRAM
CHK BY ECN NO. LIEBERT APS
J. FUCHIK 15 /20KVA, 10/16 BAY 200/100- 240/120 V EMERSON_
REF. DWG. ORDER NO. 50 /60HZ 2PH XFMR -FREE UPS DWG. NO. I DATE I REV. # 1 1050 DEARBORN DPo�
APS2002 12/23/13 1 COWMBU& OHIO 43229 Netwror Pb
-ILE NAME:
r- 17.3" [440mm]
14
FRONT VIEW
�1
22.9"
[581 mm]
Ea � I
9.6"
6.9" [243mm]
REAR VIEW
= 31.5" [799mm]
RIGHT SIDE VIEW
24.7"
[6927mm]
27.4"
[695mm]
3.6" [92mm]
-� 1.0" [24mm] 1
1
6.1,.
[154mm]
2.9"
[72mm]
4.6"
'Oily r O' [117mm]
[36mm]
BOTTOM VIEW
DRAWN BY SHEET NO.
K. STACY 1 OF 1 OUTLINE DRAWING
CHK BY ECN NO. LIEBERT APS
J. FUCHIK 15KVA, 10 BAY, 200/100- 240/120V EMERSON_
REF. DWG. ORDER NO. 50 /60HZ 2PH XFMR -FREE UPS DWG. NO. DATE REV. # 1050 DEARBORN DPo�
APS1003 I 12/26113 I 1 I COWMMM 01410 4432" Netwnit Po1w
ILE NAME:
DRAWN BY
K. STACY
CHK BY
G. FUNK
REF. DWG.
—ll� 17.3" [440mm]
ti
FRONT VIEW
28.0° [712mm]
38.1 "
[968mm]
TTI r
RIGHT SIDE VIEW
3.6" [92mm]
1
r-71 0" [24mm] 1
2.9" [154mm]
[72mm]
� T �
4.6"
[117mm]
1.4" I�
[3smm] BOTTOM VIEW
DWG. NO. DATE REV. # 1 1050 DEARBORN DRIVE EMERSON..
P.O. OX APS1007 8/20/13 0 COLUMBUS. OHIO183229 Network Power
FILE NAME:
0
REAR
VIEW
SHEET NO.
1 OF 1
OUTLINE DRAWING
ECN NO.
HEBERT APS
14 BAY EBC
ORDER NO.
28.0° [712mm]
38.1 "
[968mm]
TTI r
RIGHT SIDE VIEW
3.6" [92mm]
1
r-71 0" [24mm] 1
2.9" [154mm]
[72mm]
� T �
4.6"
[117mm]
1.4" I�
[3smm] BOTTOM VIEW
DWG. NO. DATE REV. # 1 1050 DEARBORN DRIVE EMERSON..
P.O. OX APS1007 8/20/13 0 COLUMBUS. OHIO183229 Network Power
FILE NAME:
0 0
® UPSSHOWN
FOR REFERENCE ONLY
L•ST•�� /��'— 'GL�3T
4 � C
e e
30"
(762)
MAINTENANCE BYPASS CABINET
MAY BE POSITIONED TO LEFT OR RIGHT OF UPS
NOTES
1) INSTALL IN ACCORDANCE WITH NATIONAL AND LOCAL ELECTRIC CODES.
2) ALL DIMENSIONS ARE IN INCHES AND (mm)
3) UNIT WITH TRANSFORMER REQUIRES GEC CONNECTION REFER TO THE INSTALLATION AND USERS
MANUAL, SL- 23960.
4) INPUT AND OUTPUT WIRES SHOULD BE RUN IN SEPARATE CONDUIT.
5) MINIMUM OPERATIONAL CLEARANCE REQUIRED: 12' (305) FRONT AND REAR FLEXIBLE CONDUIT
RECOMMENDED FOR SERVICE ACCESS.
6) SHIPPING BRACKETS MAY BE USED TO SECURE UNIT TO FLOOR.
7) PALLET DIMENSIONS: 3TW x 42 5'D x 9 "H (914 x 1080 x 228)
8) MAX WEIGHTS -
UNIT WITH ISO TRANSFORMER 275 LBS (125kg), SHIPPING WEIGHT 350 LBS (159kg)
UNIT WITHOUT ISO TRANSFORMER: 85 LBS (39kg), SHIPPING WEIGHT 160 LBS (73kg)
BYPASS SWITCH
DOOR LATCH AND
LOCKOUT PROVISIONS
OUTPUT BREAKER
S
UPS OUTPUT INDICATOR � e
BYPASS INDICATOR
BYPASS SWITCH
UPS INPUT INDICATOR
30.4
UPS INPUT BREAKER • • (7755)
e
tl
CONFIGURABLE OUTPUT
HARDWARE OUTPUT
(STANDARD)
e •
INPUTS TO
•
UPS
UTILITY INPUT
OUTPUT FROM UPS
m�T7
9.5"
26.5"
(3) 1 -1/4" CONDUIT
(241) ~
(700)
-�
FRONT
SIDE
DRAWN BY
SHEET NO.
R LYLES
1 QF 1
OUTLINE DRAWING
CHK BY
ECN NO.
MAINTENANCE BYPASS CABINET (MBC)
J GRFTZ
CONDUIT CONNECTIONS
NFINITY /UPSTATION GXT
REAR
REF. DWk,
ORDER NO.
e
tl
CONFIGURABLE OUTPUT
HARDWARE OUTPUT
(STANDARD)
e •
INPUTS TO
UPS
UTILITY INPUT
OUTPUT FROM UPS
(3) 1 -1/4" CONDUIT
CONNECTIONS
. 0 0%
-�
(2)1/2 "CONDUIT
CONNECTIONS
4.8"
MAIN INPUT, 1 -1/4" & 2"
CONDUIT CONNECTIONS
REAR
DWG. NO.
MNF000 -01
REV. NO. DATE
N 1 7/14/04
FILE NAME MNFOOO-01
�i Liebert EMERSON.
P.O. BOX 29188
COLUMBUS, OHIO 43229 NE&AD& '
>)
1
no]
�
(<
K. STACY
1 OF 1
no�
�<
ECN NO.
\�
G. FUNK
e
15KVA, 10 BAY, 200/100- 240/120V
REF. DWG.
ORDER NO.
50 /60HZ 2PH XFMR -FREE UPS
-
�)
oil
�(
IuuJ
( o1:
IooJ
//,
\C�) u,
Ioo
•
3 Il \ 1�)
• �• e •
}e
�J
BATTERY CABINET LIEBERT APS
FRONT VIEW
DRAWN BY
SHEET NO.
K. STACY
1 OF 1
LINE UP DETAIL
CHK BY
ECN NO.
LIEBERT APS
G. FUNK
15KVA, 10 BAY, 200/100- 240/120V
REF. DWG.
ORDER NO.
50 /60HZ 2PH XFMR -FREE UPS
•t,A�J � �• v0000 oa___ __,__
- - - - -- • a :eeo 000mo
- - - -- - - - -- - - - -osoo -
I------------ - - - -- - - - - - - - - - - -----
--- - ------------ - - ----- ..... ----- -----
LIEBERT APS BATTERY CABINET
REAR VIEW
DWG. NO. DATE REV. # 1050 DEARBORN DRIVE EMERSON
APS4003 8/21113 0 COLUMeus OHIO 43229 Network Power
-ILE NAME:
B 7 1 6 5 0
MAINTENANCE BYPASS
ONm — _ _ _
THESE ( LINKS WITHOUT TRANSFORME 0 1R NOT REIEASED rz). t
FORWAL NPUT FEE0 RELEAD IOR
PROOUCTKNJ yty� 0.wEB6TER
TB/
ADDED CHART C AND NOTE R
OVER
T J] 2 CBt FOR
CONNEGTKIN LPs MOO 0.
FEEDER � — — .� / � — , I CORRECTEOIPS UNT GE�
p tsff OHeeTq �' — — — L1 IAYP] I IA8P1 —( M
IGVEDTDT B]I
CORRECTED NIBS UNIT GNDA, p
SSE 1 ADDED CHITS DBE TOCLARIFY
SWI Tall S OROIMD �0 SINGLE DUAL FEED
I DUAL FEED CONFIG. 1 — — — — oEn I I I .wa Cal Z' I s OU UTILITY s- POSITION I OUTPU- (T.) I FIGURATIONS Ecry E1BB2s7
1 761 (UPS FEEDER 14 3C �pV
IIJTIB7 BYPASS FEEDER ONYJ
1J7•J2,IR REMOVED I I I I _� 2�u 2W.2� N.GNC U� I 1a 208V 1
IJ] I 1 OUT 1J 1ADV' 1
A yJ TO LOAD I td,3 1NN I
TB2 ISEECNrRTN BYPASS 1 24 208V 1
MAHWM I J I I I "' �e I ) '� J I 1. 208V• 1
MEDERO L1 L J _ - -L_ TOOPTIONONLYON UPS I 2a 208V• I
AU X SWITCH TB8 MODELS NMBNMW 2tl, 2. +N. ONO I 1a 2M I
CHART NRT 1 c — — J S AND NMSHlVN1 4.3 12V 1 —
SINGLE FEED CONFN;. — uwP2 I NC I BYPASS I 2a 2MV• I
I T81 1NOCONNECTION _ — _ Np I IN 1DOJ I
1782 UPS 6 BYPASS FEED I �] �nFRI THESE VOLTAGES CIUNGE BASED ON
IJ1• J2, JUMPERS FACTORY TBA SW11N UPS DR BYPASS POSITKIN
IJ3 (INSTALLED � J_ 1
TB]
L1 2
2 _ ]
CHART CHART C
UT LYRCIATBREAKER M NFINTf Y UPS B
INP
ICSIJONLYNNSTALLEDIN 2dSp I 4.16KVA UPS UNITS 20KVA UPS UNffB
a 1NLVA UPS UNITS.
1 N'BUT CIRCWTBREAKHI 1 NO, OF NO, OF NO* OF W. OF
FOR "VA UPS UNITS IS FRAME BATTERY POWER FRAME BATTERY POWER
CUSTOMER PRONGED S� MODULES MODULES 8� MODULES MODULES
TBt UPSTREAM. PavER E INTELLIGENCE x�
�T _ 18 BAY 7 MAX 8 MAX I 112 BAY 11 MAX S MAX
2 m Cal /� _
�pAIT 112 BAV 11 MAX 6 MAX
2 I 1 FILTER FIETTER r •� / £ I
rl rL •� ,U n T ` ^2
e & c DOMTACT00.
OND 3
�5 TOAPPROVED
I DEC I SGECCONNECTK]N
f COMMMON
GROUND
BATTERYM EINTERFACE rAFi
l i CONTROL MDDJLE INTELLIGENCE Fj I —
I
-� OPipNAI SECOFDCONTROL NOIXILE F+ I
— L 1 USER INTERFACE F� I I R41A "'"Y auw"'roHO I w.vcu,Ma wosm.nR�
L _ coFNECTDR _ _ �_ _ _ _ _ — E Eo
111 31 ]I pl tic F PARTS LIST
l � Lieberr
POWER IMTEAKLNOTE
A EXTENDEDBATTERY _ — CONTROL FABRICATE FROM THE MATERAL SPECIFIED N > NFINITY UPS AND A
CABINET / I ACCORDANCE NTH THE CURRENT MAINTENANCE BYPASS
/ I srroT LEBERVASE SEUREDOECF(CATIONOtAS WITHOUT LINE DIAGRAM
(OPTIONAL.) A wl0 OTIERTEN SPEERMSP CMTIONNG SINGLE LINE DUIGRME
®1 E 1 sass I E700360
r 'A. WEBSTER q" 9127101 NONE I ,�T+ =' InM 'i'-
RrNroIAEINTERFACE - J
� x ots mo T. CHATWIN °•" 3/16/02 ¢ANF
BArre ANGUUB *r 1 ®"A. WEBSTER °" 3/18/02 ec7 01748 11/112 UP
8 7 6 5 Q 4 3 2 1
[I
Amazon.com: CyberPower Smart App Online OL10000RT3UTF - UP...
Your Business: City of Ocoee
amazonbusiness
Electronics 9 kW UPS
http://www.amazon.com/CyberPower-Smart-App-Online-OLIOOOO...
® J.'s Account for Business Wish List
Departments Sell on Amazon Business Help BUSINESS SOLUTIONS 'Learn more
All Electronics Deals Best Sellers TV & Video Audio & Home Theater Computers Camera & Photo Wearable Technology Car Electronics & GPS
Sack to search results for "9 kW UPS'
® CyberPower Smart App Online Share
rM 9nnnnDT'2l ITC I IDS - 9 kW -
$6,900.74 +Free Shipping
. In Stock. Sold by Moon Tech
■ ing 1 -Click ordering is not available for this
item.
■ ind sold by Moon Tech
29 when you choose
Ship to:
J. Allison Butler- OCOEE
e Output: 120VI Voltage
Add to Wish List
a / Form Factor:
)epth: 15.75 Inch) Height:
-kj Header/ Model:
ad (W): 9 KWI Power
Have one to sell? Sell on Amazon
i Type: UPS Battery)
lattery Capacity: 9 Ahl
I Run Time: 11 min at
Sponsored by Other Brands
:ontrol Panel,Removable
ViewSonic PJD782OHD
1080p 3D Home Theater...
ompliant USB Port,Serial
(285)
MP / HTTP Remote
,pe: 3 years limited
>�,- ±err$577.00
Prepare for Storm Season
Tool and supplies to weather the storm. Shop
Roll over image to zoom in Generators, Backup Power, Emergency
Supplies, and more.
Special Offers and Product Promotions
• Unlimited Cloud Storage: Never run out of space for all your photos, videos, and files with unlimited storage plans from Amazon Cloud
Drive. Learn more
• Your cost could be $6,830.74 instead of $6,900.74! Get a $70.00 gift card instantly upon approval for the Amazon.com Rewards
Visa Card. Apply now.
Technical Details
Brand Name: CyberPower Systems
Model Number: OL10000RT3UTF
Item Weight: 492 pounds
1 of 3 7/21/2015 8:03 AM
Amazon.com: CyberPower Smart App Online OL10000RT3UTF - UP..
Product Description
http: / /www.amazon.com/CyberPower- Smart- App - Online -OL 10000...
CyberPower Smart App Online OL1000ORT3UTF - UPS - AC 200 -240 V - 9 kW - 10000 VA 9 Ah - RS -232, USE; - 19 output connector(s) - 9U.
The CyberPower Smart App Online OLIOOOORT3UTF rack/tower uninterruptible power supply (UPS) with Step -down Transformer, LCD Control
Panel, and pure sine wave output safeguards mission - critical servers, data center and telecom equipment, VoIP, and internetworking
hardware that require seamless power correction. Its Online Double Conversion topology is generator compatible and delivers consistent and
clean standard 120V or 200 -240V AC power with zero transfer time to protect connected equipment and prevent costly business
interruptions. Auto- bypass insures connected equipment continues to operate seamlessly when an overload or internal fault is detected. The
LCD Control Panel provides 38 different settings to check status and customize the operating settings for the OL1000ORT3UTF, plus it can be
removed and mounted separately from the UPS for ease of use regardless of where the UPS is installed. Functions include menus for checking
power status on 16 different parameters, 19 settings for setup, control, and testing of the UPS, and 3 selections for event logging. With a
Product Details
Item Weight: 492 pounds
Shipping Weight: 492 pounds (View shipping rates and policies)
ASIN:BOOP9G3AU2
Item model number: OL1000ORT3UTF
Average Customer Review: Be the first to review this item
Product Warranty: For warranty information about this product, please click here
Date first available at Amazon.com: November 5, 2014
Would you like to update product info, give feedback on images, or tell us about a lower price?
Customer Questions & Answers
Have a question? Ask the owners here
Typical questions asked about products:
Is the item durable?
Is this item easy to use?
What are the dimensions of this item?
Customer Reviews
There are no customer reviews yet.
5 star Share your thoughts with other customers
4 star
3 star
2 star
1 star
Ad feedback ':-.'
Customers Viewing This Page May Be Interested In These Sponsored Links (what'sths?)
UPS Service & Parts gJ
www.millenniumups.com/ - Eaton Mitsubishi APC /MGE Liebert GE 1 Yr Warranty Call Now For A Quote!
Power Backups from $25 rF
www.upsforiess.com/ - Save up to 90% on major brand Battery backups/UPS's.
Go Straight to the Source [T
www.egreeneonline.com/ - Manufacturer of Bank & CU Supplies Small Orders, Custom Imprints!
Your Recently Viewed Items and Featured Recommendations
Inspired by your browsing history
Page 1 of 6
2 of 3 7/21/2015 8:03 AM
Liebert
Innovative Support Systems, Inc.
1030 Sunshine Lane, Suite 1000
Altamonte Springs, FL 32714
FAX: (407) 682 -0024 PH: (407) 682 -7570
COMPANY: PRESIDIO NETWORKED SOLUTIONS
ATTN:
FAX:
FROM: SEAN DEVANEY
PROJECT: CITY OF OCOEE - DATACENTER UPS
EMERSON -
PROPOSALM
PAGES
DATE:
Q02333887
153625LABSD
4
Jul 21, 2015
We are pleased to provide our quotation for the following Liebert / Emerson Network Power system for your
consideration on this project.
One (1) 3 Ton Nominal Capacity 208/230 -1 -60 Volt Evaporator(s), DataMate Model DME037E -PH7.
• Includes evaporator coil, filter drier, thermal expansion valve, R -407C refrigerant unit charge and quick -
connect female couplings on both the suction and liquid lines.
• Electric Reheat
• Steam Canister Humidifier
One (1) Liebert Model PFH037A -PL7 208/230/1 Outdoor Condensing Unit.
• R -407C refrigerant unit charge
• Designed for outdoor ambient of 95 °F.
Ship Loose Items:
• 1 Sweat Adapter Kit (3 Ton)
Services Included:
• 1 Year PARTS ONLY Warranty
• 2nd Through 5th Year COMPRESSOR ONLY Warranty Included
Terms & Conditions:
- Quotation Valid for 45 days
- Terms are Net 30 Days, subject to manufacturer's approval
- Liebert standard Terms & Conditions apply
- Please address Purchase Orders to:
Innovative Support Systems, Inc.
1030 Sunshine Lane, Suite 1000
Altamonte Springs, FL 32714
Net Price, FOB FACTORY, Freight Included, Less Tax $ 7.710.00
ADD for Field Installed Condensate Pump, if required $ 315.00
ADD for Factory Authorized Warranty Inspection /Start Up $ 500.00
ALL ASPECTS OF INSTALLATION TO BE PROVIDED BY OTHERS
SEAN DEVANEY
Account Representative
7/22/2015 Liebert- Proprietary Page 1 of 4
LIMITED WARRANTY FOR THERMAL MANAGEMENT PRODUCTS
This Warranty is given ONLY to purchasers who buy for commercial or industrial use in the ordinary course of each
purchaser's business.
General:
Liebert Corporation products and systems are in our opinion the finest available. We take pride in our products and are pleased
that you have chosen them. Under certain circumstances we offer with our products the following One Year Limited Warranty
Against Defects in Material and Workmanship.
Please read your Warranty carefully. This Warranty sets forth our responsibilities in the unlikely event of defect and tells you
how to obtain performance under this Warranty.
ONE YEAR LIMITED WARRANTY
AGAINST DEFECTS IN MATERIAL AND WORKMANSHIP
PRODUCTS COVERED:
This warranty applies to all Liebert branded Precision Cooling products, included but not limited to, unless specifically noted,
Liebert Mini- Mate2TM, Liebert DataMatcTm, Liebert ChallengerTM 3000, Liebert Challengefm ITR, Liebert Industrial Cooling
Series, Liebert Condenser, Liebert MC, Liebert Drycooler, Liebert DSTM, Liebert DSE, Liebert CWTM, Liebert CRVTM, Liebert
InteleCool2®, Liebert XDTM, Liebert DCW, Liebert CWC, Liebert DSC, Liebert EVI, Liebert EVD, Liebert HPC
Terms of Warrantv:
As provided herein, the Liebert product is warranted to be free of defects in material and workmanship for a period of one year
from the start-up date provided the product Warranty Inspection sheet is returned to Liebert, start-up occurs within six (6) months
of the Liebert shipping date, and the product has been stored in a suitable environment prior to start-up. The start-up date will be
determined only from the completed inspection and start-up sheet received with the product. If the product start-up sheet is not
returned to Liebert, the Liebert product is warranted to be free of defects in material and workmanship for a period of thirteen
(13) months from date of product shipment by Liebert. The shipment date will be determined only from the Liebert bill of lading.
In addition, for products installed in the United States or Canada, the drive package contained in the Liebert DS product and
Liebert InteleCool28 Compressor is warranted to be free of defects in material and workmanship for a period of five (5) years
from the above referenced dates, as applicable. The drive package contained in the Liebert DS product consists of blower belts, a
blower shaft, blower bearings, a blower pulley, and motor sheave.
If any part or portion of the Liebert product fails to conform to the Warranty within the Warranty period, Liebert, at its option,
will furnish new or factory remanufactured components for repair or replacement of that portion or part, or Liebert may furnish
User with a replacement product. Liebert will not assume any labor or shipping charges associated with repair or replacement of
the Liebert product or part thereof. This is a Parts Warranty ONLY that does not include Services; all Services shall be provided
by a qualified Service provider. Upon Liebert's request this warranty may require recorded proof of Quarterly product
maintenance completed by a qualified service provider. If it is determined that failure occurred due to lack of maintenance,
Liebert maintains the right to deny the warranty claim.
Warrantv Extends to First Purchaser for Use. Non - transferable:
This Warranty is extended to the first person, firm, association or corporation for whom the Liebert product specified herein is
originally installed for use (the "User ") in the fifty United States or Canada. This Warranty is not transferable or assignable
without the prior written permission of Liebert.
ASSlgnment of Warranties:
Liebert assigns to User any warranties which are made by manufacturers and suppliers of components of, or accessories for, the
Liebert product and which are assignable, but Liebert makes NO REPRESENTATIONS as to the effectiveness or extent of such
warranties, assumes NO RESPONSIBILITY for any matters which may be warranted by such manufacturers or suppliers and
extends no coverage under this Warranty to such components or accessories.
Drawings. Descriptions:
Precision Cooling Systems Warranty Rev. 9/10/2013 SL-01000
Liebert warrants for the period and on the terms of the Warranty set forth herein that the Liebert product will conform to the
descriptions contained in the certified drawings, if any, applicable thereto, Liebert's final invoices, and to applicable Liebert
product brochures and manuals current as of the date of product shipment ( "Descriptions "). Liebert does not control the use of
any Liebert product. Accordingly, it is understood that the Descriptions are NOT WARRANTIES OF PERFORMANCE and
NOT WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE.
Warrantv Claims Procedure:
Within a reasonable time, but in no case to exceed thirty (30) days, after User's discovery of a defect, User shall contact the local
Liebert sales representative from whom the product was purchased. User may contact Liebert at 1 -800 LIEBERT (543 -2378) for
local Liebert sales representative information. Subject to the limitations specified herein, the Liebert sales representative will
arrange for a Liebert service representative to repair or replace the non - conforming Liebert product warranted hereunder, without
charge for materials. User shall bear all labor or shipping charges associated with repair or replacement of the product herein.
Warranty coverage will be extended only after the Liebert service representative's inspection discloses the claimed defect and
shows no signs of treatment or use that would void the coverage of this Warranty. All defective products and component parts
replaced under this warranty become the property of Liebert.
Warrantv Performance of Component Manufacturers:
It is Liebert's practice, consistent with its desire to remedy Warranty defects in the most prompt and effective manner possible, to
cooperate with and utilize the services of component manufacturers and their authorized representatives in the performance of
work to correct defects in the product components. Accordingly, Liebert may utilize third parties in the performance of Warranty
work, including repair or replacement hereunder, where, in Liebert's opinion, such work can be performed in less time, with less
expense, or in closer proximity to the Liebert product.
Items Not Covered By Warranty:
THIS WARRANTY DOES NOT COVER DAMAGE OR DEFECT CAUSED BY misuse, improper application, wrong or
inadequate electrical current or connection, inadequate water or drain services, negligence, inappropriate on site operating
conditions, corrosive atmosphere, failure to adequately maintain the Product using a qualified Service provider, repair by non-
Liebert designated personnel, accident in transit, tampering, alterations, a change in location or operating use, exposure to the
elements, Acts of God, theft or installation contrary to Liebert's recommendations or specifications, or in any event if the Liebert
serial number has been altered, defaced, or removed.
THIS WARRANTY DOES NOT COVER shipping costs, installation costs, circuit breaker resetting, loss of refrigerant, or
maintenance or service items and further, except as may be provided herein, does NOT include labor costs or transportation
charges arising from the repair or replacement of the Liebert product or any part thereof or charges to remove or reinstall same at
any premises of User.
THE PRODUCTS LISTED IN THIS WARRANTY ARE NOT FOR USE IN ANY SAFETY APPLICATIONS OR WITHIN
THE CONTAINMENT AREA OF A NUCLEAR FACILITY OR WHERE THE PRODUCTS HAVE POTENTIAL FOR
DIRECT PATIENT CONTACT OR WHERE A SIX (6) FOOT CLEARANCE FROM A PATIENT CANNOT BE
MAINTAINED AT ALL TIMES. THE PRODUCTS LISTED IN THIS WARRANTY MAY BE PLACED DIRECTLY OVER
PATIENTS OR DIAGNOSTIC AND SURGICAL EQUIPMENT ONLY WHERE THE END -USE CUSTOMER HAS SIGNED
LIEBERT'S HEALTHCARE APPLICATION SALES AGREEMENT, OTHERWISE THE WARRANTY IS VOID.
REPAIR OR REPLACEMENT OF A DEFECTIVE PRODUCT OR PART THEREOF DOES NOT EXTEND THE ORIGINAL
WARRANTY PERIOD.
Limitations:
THIS WARRANTY IS IN LIEU OF AND EXCLUDES ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
USER'S SOLE AND EXCLUSIVE REMEDY IS REPAIR OR REPLACEMENT OF THE LIEBERT PRODUCT AS SET
FORTH HEREIN.
IF USER'S REMEDY IS DEEMED TO FAIL OF ITS ESSENTIAL PURPOSE BY A COURT OF COMPETENT
JURISDICTION, LIEBERT S RESPONSIBILITY FOR PROPERTY LOSS OR DAMAGE SHALL NOT EXCEED THE NET
PRODUCT PURCHASE PRICE.
Precision Cooling Systems Wa my Rev. 9/10/2013 S1.1O1000
IN NO EVENT SHALL LIEBERT ASSUME ANY LIABILITY FOR INDIRECT, SPECIAL, INCIDENTAL, EXEMPLARY
OR CONSEQUENTIAL DAMAGES OF ANY KIND WHATSOEVER, INCLUDING WITHOUT LIMITATION LOST
PROFITS, BUSINESS INTERRUPTION OR LOSS OF DATA, WHETHER ANY CLAIM IS BASED UPON THEORIES OF
CONTRACT, NEGLIGENCE, STRICT LIABILITY, TORT, OR OTHERWISE.
Miscellaneous:
NO SALESPERSON, EMPLOYEE OR AGENT OF LIEBERT IS AUTHORIZED TO ADD TO OR VARY THE TERMS OF
THIS WARRANTY. Warranty terms may be modified, if at all, only by a writing signed by a Liebert officer.
Liebert obligations under this warranty are conditioned upon Liebert timely receipt of full payment of the product purchase price
and any other amounts due. Liebert reserves the right to supplement or change the terms of this Warranty in any subsequent
warranty offering to User or others.
In the event that any provision of this Warranty should be or becomes invalid and/or unenforceable during the warranty period,
the remaining terms and provisions shall continue in full force and effect.
User shall complete the attached User Information Card and forward it to Liebert within thirty (30) days of receipt of the Liebert
product.
This Warranty shall be governed by, and construed under, the laws of the State of Ohio, without reference to the conflict of laws
provisions thereof.
This Warranty represents the entire agreement between Liebert and User with respect to the subject matter herein and supersedes
all prior or contemporaneous oral or written communications, representations, understandings or agreements relating to this
subject.
Precision Cooling Systems Warranty Rev. 9/10/2013 SL -01000
■ Precision Cooling
For Business - Critical ContinuityT"
Lieberr DataMate'
Economical, Space- Saving Cooling Systems For Sensitive Electronics
EMERSON.
Precision Cooling Designed
To Fit The Smallest Spaces
Liebert DataMate precision environmental systems are the perfect solution for cramped quarters requiring temperature
and humidity control for sensitive electronics. And while the systems are matched to meet the needs of computers, they
are also designed to be convenient for the people sharing space with the protected equipment.
Space- saving. The slim, compact Liebert
DataMate may be wall- or floor - mounted, and
requires minimal service access, limiting floor
space requirements.
High sensible cooling capacity. Unlike
"comfort" air conditioners, Liebert precision
cooling systems are designed for the cooling
requirements of electronic equipment -80%
of the capacity dedicated to the removal of
dry "sensible" heat, and 20% for control of
humidity.
Reliable. The Liebert DataMate installed -
base is a testimonial to system reliability.
Components include a compressor; a
high efficiency copper -tube, aluminum -fin
evaporator coil; and a double inlet, direct drive
fan.
Outdoor Air Cooled. Suitable for roof or
ground level site. The condensing unit is
designed for operation as low as -30* F.
Water/Glycol Cooled Remote. Utilizes an
existing water or glycol loop. Condensing
unit is located under the raised floor or above
the dropped ceiling.
u
Quiet. The units are designed to operate
quietly with the compressor vibration -
isolated from the chassis. The cabinet is also
insulated to further ensure quiet operation.
On many models, the compressor- containing
condensing unit can be remotely located to
further reduce noise levels in the controlled
space. Quiet -Line outdoor condensing units
are available for 6 -8 dba sound level reduction
over the standard models.
Flexibility options. Liebert DataMate 60Hz
systems are available in capacities of 1.5, 2 and
3 tons in air, water, glycol, and a self- contained
3 ton chilled water model (3 -Ton models only
in 50Hz). Systems may be configured as self -
contained or separated from the condensing
unit, depending on the model.
l
J
Indoor Air Cooled. For high -rise and other
applications where roof or ground level locations
are impractical. May be located above the
dropped ceiling and ducted to the outside.
Designed for operation down to -20'F ambient.
WaterlGlycol Cooled Integral. Totally
packaged. A single power and water supply
connection puts the unit in operation.
Easy installation. All Liebert DataMate
components are precharged, and require
no field brazing, evacuation or charging.
Precharged refrigerant lines are available to
connect evaporator and remote condensing
unit modules when required.
Two -speed fan operation. High speed
provides quiet operation and maximum
cooling. Low speed provides maximum
dehumidification and lowest sound level.
The speed can be automatically or manually
selected.
Corrosion - Resistant Cabinet.
Durability is ensured with Powder Coated
Paint panels.
Chilled Water. This unit simply connects
to a chilled water loop, for quick and easy
installation.
Specifications
Indoor and outdoor condensing unit options maximize Liebert
Data Mate installation options for better system flexibility. Outdoor
models are available in Quiet -Line and High Ambient versions.
0
60Hz '
SOHz
Air - Cooled System
with Outdoor Condensing Unit Split System with Indoor Condensing Unit Split
with Outdoor Condensing with Indoor Condensing
System
Unit Split System Unit Split System
Evaporator
DME020E
DME027E
DME031E OME027E
DME037E
DME037E DME037E
Condensing Unit
PFH020A
PFH027A
PFH037A MCD24A
I
MCD36A
PFH036A MCD35A
Net Capacity Data' - kW (Btuh) - High Fan Speed
Total
5.40 (18,500) I
7.10 (24,200)
10.1 (34,600) 6.85 (23,300) 9.60 (32,700)
9.90 (33,800) 9.45 (32,300)
80 °F DB (26.7 °C)
jl
38 %RH Sensible
5.40 (18,500)
7.10 (24,200)
9.70 (33,100) 6.85 (23,300) 9.40 (32,000)
8.85 (30,200) 8.65 (29,500)
°C) Total
5.05 (17,200)
6.60 (22,500)
9.75 (33,200) 6.35 (21,700) 9.15 (31,300)
9.55 (32,500) 9.10 (31,100)
75 °F DB (23.9
I
45 %RH Sensible
4.90 (16,700)
6.50 (22,200)
8.60 (29,400) 6.35 (21,600) 8.35 (28,500)
7.90 (26,900) 7.70 (26,300)
°C) Total
4.85 (16,500)
6.35 (21,700)
9.50 (32,400) 6.10 (20,800) 8.95 (30,600)
9.30 (31,800) 8.90 (30,400) 1
72 °F DB (22.2
I
50 %RH Sensible
4.50 (15,400)
6.05 (20,600)
7.95 (27,100) 5.90 (20,100) 7.70 (26,200)
7.30 (24,900) 7.10 (24,300)
1
60Hz
50Hz
Water Cooled
Glycol Cooled
Water Coolcd
Glycol Cooled
Evaporator
DME020E
DME027E
DME037E
DME020E
DME027E
DME037E DME037E
DME037E
Condensing Unit
DMCO22WG
I
"DMCO29WG)
I
"DMC040WC
DMCO22WG
I
"DMCO29WG�
- DMC040WG/ MCD37W
MCD37W
MCD26W"
MCD38W"
MCD26W"
MCD38W"
Net Capacity Data' - kW (Btuh)
- High Fan Speed
80 °F DB (26.7 °C) I Total
5.90 (20,100)
7.95 (27,200)
11.4(38,900) 5.15 (17,600) 6.75 (23,000)
9.65 (32,900) 11.3 (38,700) 9.30 (31,800)
38 %RH
Sensible
5.80 (19,800)
7.90 (27,000)
10.3 (35,300) 5.15 (17,600) 6.75 (23,000)
9.40 (32,100) 9.55 (32,600) 8.60 (29,300)
I
Total
5.50 (18,800)
7.55 (25,800)
11.0 (37,400) 4.80 (16,300) 6.25 (21,300)
9.20 (31,400) 11.0 (37,400) 8.95 (30,500)
°F DB (23.9 °C)
175
45 %RH
Sensible
5.15 (17,600)
7.10 (24,200)
9.20 (31,400) 4.75 (16,200) 6.25 (21,300)
8.35 (28,500) 8.55 (29,200) 7.60 (26,000)
°C) I
Total
5.35 (18,100)
7.35 (25,000)
10.7 (36,600) 4.60 (15,700) 6.00 (20,500)
8.95 (30,600) 10.7 (36,600) 8.75 (29,900)
172 °F DB (22.2
50 %RH I Sensible
4.75 (16,200)
6.55 (22,300)
8.55 (29,100) 4.35 (14,900) 5.85 (19,900)
7.70 (26,300) 7.95 (27,200) 7.05 (24,000)
60 Hz I
SOHz
IEvaporator
CHILLED
I
WATER
Condensing Unit
I DME044C I
DME044C
Net Capacity Data" -kW (Btuh)
-High Fan Speed
80 °FDB(26.7 °C) I Total
10.5 (36,000)
9.1 (31,100)
38 %RH
Sensible
9.65 (32,900)
8.3 (28,200)
to i 1
V 4J
75 °FDB(23.9 °C)
Total
8.45 (28.900)
7.6 (25,900)
iiiililloumiiui '�tllViViuiiiiuhiiliifiiimiiJ'
45 %RH
Sensible
7.9s (27,100)
6.8 (23,200)
Microprocessor control system.
Standard 60Hz units are CSA certified
I
The microprocessor control system,
to the harmonized U.S. and Canadian
72 °FDB (22.2 °C) Total
7.65 (26.100)
6.6 (22,600)
with its user - friendly wall -mount display,
product safety standard, CSA C22.2 No
50 %RH
Sensible
6.90 (23,500)
5.9 (20,200)
provides precise temperature and
236JUL 1995 for "Heating and Cooling
" The netcapacity data hasfan
motor heatfactored in forall ratings
accurate alarm setpoints. Using touch-
Equipment" and are marked with the CSA
and the entering air conditions of 75 °F (23.9 °C), 45 %RH, is the
sensitive buttons, the monitor control
C - -US logo.
standard rating condition forASHRAE 127 -2007. All capacities are
panel allows you to select and display
nominal values; actual performance
will be 15%."
time, temperature, humidity, alarm
indication and other parameters.
0